Page 30
WIRELESS H2S TRANSMITTER (WT SERIES) - USER GUIDE
8.
Configure the transmitter – part 1
a.
Create a
Transmitter Name
.
b.
Enter a
Transmit Interval
in Hr:Min:Sec.
i.
See Battery Life Expectancy data in the
choose the reporting interval that best suits your needs.
c.
Select
Map to Integer Table
or
Map to Floating Point Table
.
i.
Default
Integer Table
begins at register
3001
.
ii.
Default
Floating Point Table
begins at register
7001
.
d.
Copies
: Enter the number of transmitters that you want to populate to
the project using these settings.
e.
Click
Template
to open
Edit Template
window.
f.
Modify the
Edit Template
to desired settings.
The tags listed under the
Exported Tags
will automatically be added to
the Modbus Mapping Table.
i.
H2S Level
: H2S detection level in 0.1 ppm
ii.
H2S Alarm:
Current alarm flags
0 = No Alarms, 1 = High Alarm, 2 = High-High Alarm
3 = All Alarms
iii.
Alarm 1 Status
: 0 = Off, 1 = On (alarm output state)
iv.
Alarm 2 Status
: 0 = Off, 1 = On (alarm output state)
v.
Sensor Error
: 0 = No errors, 1 = Sensor communication error,
sensor not connected (will trigger alarm state)
vi.
Days in Service
: Total number of days in service from powering on
vii.
Bump Test Count
: Total number of completed bump tests
viii.
Bump Days
: Total number of days since the last successful bump
test
ix.
Calibration Days:
Total number of days since last calibration
x.
Battery Voltage
:
Replace when ≤ 2.9 V