Page 16
WIRELESS H2S TRANSMITTER (WT SERIES) - USER GUIDE
7.
BATTERY PACK
1.
Installation
Internal battery power: 3.6 Vdc
The battery level is read under load.
Note:
Once a new battery pack is installed, it is perfectly normal to get a
reading of 3.2 to 3.3 Vdc.
The transmitter reads the battery level while under load, providing a
reliable method of monitoring battery health. Using the RF Timeout, RF
Refresh and Battery Voltage tags are strongly
recommended for
monitoring device and RF communication health.
When a new battery pack is taken from storage and initially installed, the
battery level may need to be read a couple of times to ensure a stable and
accurate reading.
Use only battery pack part number SX1000-BP3.
Disconnect the battery when the device is not in use.
Replace the
battery pack when it reaches ≤ 2.90 Vdc.
Utilisez uniquement le numéro de pièce de la batterie SX1000-BP3.
Déconnecter la batterie lorsque l'appareil n'est pas utilisé.
Remplacez la batterie lorsqu'elle atteint ≤ 2
.90 Vdc.
The transmitter contains a lithium battery pack. The lithium batteries are
regulated in transportation by the U.S. DOT (Department of Transportation)
and are also covered by IATA (International Air Transport Association), ICAO
(International Civil Aviation Organization), and ARD (European Ground
Transportation of Dangerous Goods). It is the responsibility of the shipper to
ensure compliance with these or any other local requirements. Consult current
regulations and requirements before shipping.
Содержание WT H2S Series
Страница 6: ...Page 6 WIRELESS H2S TRANSMITTER WT SERIES USER GUIDE 3 Intrinsic Safety Control Drawings...
Страница 13: ...Page 13 WIRELESS H2S TRANSMITTER WT SERIES USER GUIDE 4 NETWORKING DIAGRAM...
Страница 33: ...Page 33 WIRELESS H2S TRANSMITTER WT SERIES USER GUIDE 16 SOFTWARE MAIN SCREEN VIEW...