Setup
52
W-4510 Weigh Scale Technical Reference Manual
Calibrate the analog output by setting the mid-point (12mA) to a reference meter or DCS/PLC
reading. This reconciles any small voltage differences between this gauge and the primary
measurement control system.
Procedure 8: Setup analog output Channel #1
1. From
065 ANALOG OUTPUTS
screen, select
SET ANALOG OUTPUT SPAN
and
press ENTER
2. From
060 ANALOG OUTPUT SPAN
screen, select
SET OUT CHAN#1 SPAN
and press ENTER
3. From
078 TYPE OF ANALOG OUTPUT UNITS TO USE
screen, select either
•
USE STANDARD UNITS
•
USE RATE UNITS
Press ENTER
4.
If you select
USE STANDARD UNITS
perform the following steps:
•
From
240 SET ANALOG OUTPUT
SPAN screen, select
SET LOW LIMIT
and
press ENTER
•
From
242 SET LOW LIMIT
screen, enter the new setting and press ENTER
•
Return to screen
240
by pressing PREVIOUS SCREEN
•
From
240
screen, press SELECT to choose
SET HIGH LI
MIT and press
ENTER
•
From
244 SET HIGH LIMIT
screen, enter the new setting and press ENTER
5.
If you select USE RATE UNITS perform the following steps:
•
From
240 SET ANALOG OUTPUT SPAN
screen, select
SET LOW LIMIT
and
press ENTER
•
From
243 SET LOW LIMIT
screen, enter the new setting and press ENTER
•
Return to screen
240
by pressing PREVIOUS SCREEN
•
From
240
screen, press SELECT to choose
SET HIGH LIMIT
and press
ENTER
•
From
245 SET HIGH LIMIT
screen, enter the new setting and press ENTER
6.
Connect the write protect jumper JP17
7.
Save to EEPROM
8.
Disconnect the write protect jumper, JP17. This protects the information in the
EEPROM.
Содержание W-4510
Страница 9: ...Preface viii W 4510 Weigh Scale Technical Reference Manual Notes...
Страница 15: ...Preface xiv W 4510 Weigh Scale Technical Reference Manual Notes...
Страница 17: ...Preface xvi W 4510 Weigh Scale Technical Reference Manual Notes...
Страница 29: ...Introduction 12 W 4510 Weigh Scale Technical Reference Manual Notes...
Страница 36: ...Installation W 4510 Weigh Scale Technical Reference Manual 19 Figure 6 Typical Smart Pro dimensions...
Страница 48: ...Installation W 4510 Weigh Scale Technical Reference Manual 31 Figure 13 W 4510 terminal illustration...
Страница 125: ...Calibration 108 W 4510 Weigh Scale Technical Reference Manual Notes...
Страница 145: ...Diagnostics and repair 128 W 4510 Weigh Scale Technical Reference Manual Notes...
Страница 155: ...Appendix I Parameter blocks 138 W 4510 Weigh Scale Technical Reference Manual Notes...