INSTALLATION | Specification
62
www.ochsner.com | 982000-AIR-M2-M4-EN03.1
14.2 Heat pumps for single phase alternating
current
14.2.1 Data table
AIR 11 C11B
AIR 18 C11B
INDOOR UNIT:
Hydraulic variant
M2-1/M2-2/M2-3/M2-4
M2-1/M2-2/M2-3/M2-4
Dimensions HxWxD
[mm]
1286x600x680
1286x600x680
Hydraulic connection
DN 32 (1 1/4”) male
DN 32 (1 1/4”) male
Weight
[kg]
124
135
Casing colour
Tiger white 29/11289/grey RAL
7016
Tiger white 29/11289/grey RAL
7016
HEATING MODE PERFORMANCE DATA:
Standard point L10/W35
Heating output
[kW]
11.1
16.1
Total power consumption / operating current
[kW]/[A]
2.5 / 12.9
3.4 / 20.8
Coefficient of performance EN 14511/EN 255
4.4 / 4.7
4.8 / 5
Operating point L7/W35
Heating output
[kW]
10.2
14.8
Total power consumption / operating current
[kW]/[A]
2.4 / 12.4
3.3 / 20.5
Coefficient of performance EN 14511/EN 255
4.3 / 4.5
4.5 / 4.8
Standard point A2/W35
Heating output
[kW]
8.9
13
Total power consumption / operating current
[kW]/[A]
2.3 / 11.6
3.2 / 19.9
Coefficient of performance EN 14511/EN 255
4 / 4.2
4 / 4.3
Standard point L-7/W35
Heating output
[kW]
6.9
10.1
Total power consumption / operating current
[kW]/[A]
2.2 / 11.5
3.2 / 19.9
Coefficient of performance EN 14511/EN 255
3.1 / 3.3
3.1 / 3.3
Operating point L-10/W35
Heating output
[kW]
6.3
9.2
Total power consumption / operating current
[kW]/[A]
2.1 / 10.9
3.1 / 19.5
Coefficient of performance EN 14511/EN 255
3 / 3.3
2.9 / 3.1
Operating point A2/W50
Heating output
kW
8.5
12.3
Total power consumption / operating current
[kW]/[A]
3 / 15.5
4.3 / 26.1
Coefficient of performance EN 14511/EN 255
2.8 / 2.9
2.9 / 3.1
Operating point A2/W60
Heating output
[kW]
8.4
11.5
Total power consumption / operating current
[kW]/[A]
3.3 / 17.1
4.5 / 27.4
Coefficient of performance EN 14511/EN 255
2.5 / 2.6
2.6 / 2.8
COOLING MODE PERFORMANCE DATA:
Operating point A30/W18
Cooling capacity
[kW]
9.5
9.9
Total power consumption / operating current
[kW]/[A]
3.2 / 16.6
3.4 / 21.1
Energy efficiency ratio EER
3
2.9
Operating point A30/W7
Cooling capacity
[kW]
8.6
9.3
Total power consumption / operating current
[kW]/[A]
3.1 / 16
3.4 / 21.1
Energy efficiency ratio EER
2.8
2.7
SPECIFICATION:
Phases/nominal voltage/frequency
[~]/[V]/[Hz]
1/230/50
1/230/50
Output factor cos ϕ
0.84
0.71
Fuse
C25A
C40A
Max. operating current
[A]
20.8
30
Max. starting current/max. with soft start
[A]
97 / 48.5
160/80
Sound power level/sound pressure level (at 1 m distance)
[dBA]
44.5 / 36.5