INSTALLATION | Preparing to install the appliance
18
www.ochsner.com | 982000-AIR-M2-M4-EN03.1
9.4.1 Line lengths
»
Observe the maximum permissible line lengths for
the refrigerant lines.
»
Where the outdoor unit is positioned higher than the
indoor unit, observe the maximum permissible height
differential between the two units.
11_06_200_202_001
D
A
B
C
A + B + C
(sum of line lengths)
D
(max. height differential)
AIR 7
≤ 20 m
≤ 10 m
AIR 11
≤ 20 m
≤ 10 m
AIR 18
≤ 20 m
≤ 10 m
AIR 23
≤ 20 m
≤ 10 m
AIR 29
≤ 20 m
≤ 10 m
AIR 41
≤ 16 m
≤ 5 m
»
Where the outdoor unit is positioned lower than the
indoor unit, observe the maximum permissible height
differential between the highest and lowest points of
the refrigerant lines.
11_06_200_202_003
≤ 3500
≤ 2970
650
1180
»
Where a line routed along the ceiling is used in
conjunction with an underground connection line,
observe the maximum permissible height differential
between the highest and lowest points of the refriger-
ant lines.
11_06_200_202_002
≤ 3500
1223
9.4.2 Pipe diameter
The pipe diameter data for refrigerant lines shown below
applies as long as the following are observed:
►
A maximum of eight 90° pipe bends
►
With pipe diameters of < 35 mm, use a suitable pipe
bending tool to create the pipe bends
►
With pipe diameters of ≥ 35 mm, use type 5002 pipe
bends
►
Bending radii of ≥ 1 m are treated as straight runs
i
Information
Refrigerant lines with a pipe diameter of ≥ 35 mm
are created from rigid copper pipes in 5 m lengths.
»
With underground refrigerant lines, provide an
assembly shaft at connection sites to facilitate
soldering and maintenance work.