INSTALLATION | Appliance installation
32
www.ochsner.com | 982000-AIR-M2-M4-EN03.1
Material damage
Unsuitable fill water can damage your system due
to scaling and corrosion.
»
If necessary, ensure that the fill water is pro
-
fessionally softened and demineralised.
10.3.2 Safety valve drain
i
Information
The indoor unit has an internal safety valve (DHW,
heating).
»
Observe national and regional regulations re-
garding the design of the drain and prescribed
regular operational tests.
i
Information
The maximum operating pressure of the heat
transfer medium is 3 bar. However, due to closing
pressure differences, the safety valve may begin
to open from a pressure of 2.4 bar.
If the valve is triggered, the water exits via a hose on the
rear of the indoor unit.
»
The safety valve drain should be dimensioned such
that the water can drain unobstructed via an open
and readily visible waste water drain.
»
Install the hose with a consistent fall to the drain.
Avoid kinking the hose.
11_02_200_202_01_023
10.3.3 Filling the heating system
On delivery, the 3-way switching module will be in the
“heating mode” position.
You can find information on subsequent manual switching
of the 3-way switching module in the controller operating
instructions (DHW circuit/relay test).
»
Fill the heating system with suitable fill water using
the drain and fill valve.
11_02_200_202_01_027
1
1
Drain and fill valve with hose screw connector (spe
-
cial thread M21x1.5)
i
Information
The drain and fill valve has a special thread
(M21x1.5) for the hose screw connector.
»
Take care of the hose screw connector provid-
ed and keep it close to the heat pump.
11_02_200_202_01_028
1
2
4
3
1
Drain and fill valve
2
Locking ring for closing and opening the drain and fill
valve
3 Hose screw connector (special thread M21x1.5)
4 Cover
Venting the heating system
On the AIR 7, AIR 11 and AIR 18 (M2 hydraulic variant)
indoor units, the multifunctional assembly (MFA) has a
quick-action air vent valve for venting the heating system.
»
Before venting, open the quick-action air vent valve
on the multifunctional assembly (MFA). Do this by
pulling the red cover on the valve.
Material damage
During venting, water can escape from the air out-
let on the quick-action air vent valve.
»
Ensure that the electronics in the indoor unit
do not become wet.