INSTALLATION
| Specification
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 63
AIR 11 C11B
AIR 18 C11B
ELECTRIC BOOSTER HEATER (M2-1, M2-3):
Phases/nominal voltage/frequency
[~]/[V]/[Hz]
1/230/50
1/230/50
Max. output
[kW]
8.8 (2.9 / 2.9 / 2.9)
8.8 (2.9 / 2.9 / 2.9)
Max. operating current
[A]
38.3 (12.8 / 12.8 / 12.8)
38.3 (12.8 / 12.8 / 12.8)
CONDENSER:
Type
Plate heat exchanger
Plate heat exchanger
Material
Stainless steel 1.4301
Stainless steel 1.4301
Quantity
[pcs]
1
1
Max. refrigerant operating pressure
[bar]
30
30
Max. heat transfer medium operating pressure
[bar]
3
3
Heat transfer medium temperature differential
[K]
5
5
Application range
[°C]
65
65
Heat transfer medium
Water
Water
Test pressure
[bar]
45
45
Heat transfer medium flow rate
[m³/h]
1.7
2.2
Internal pressure differential
[mbar]
205
324
Flow meter
built-in
built-in
Heat sink circulation pump (heat generator pump)
internal
Yonos Para 25/7.5
Yonos Para 25/7.5
Residual head I heat sink system, external, incl. flow me-
ter
[mbar]
446
175
REFRIGERANT CIRCUIT:
No. of refrigerant circuits
[pcs]
1
1
Heat transfer medium
R407C
R407C
Refrigerant full charge
[kg]
9.0
9.0
Defrost technology
Hot gas
Hot gas
COMPRESSOR:
Type
Fully hermetic/scroll
Fully hermetic/scroll
Quantity
[pcs]
1
1
Output levels
1
1
Speed
[rpm]
2900
2900
Voltage/frequency
[V]/[Hz]
230 / 50
230 / 50
Max. operating current
[A]
19.4
28.6
FAN (OUTDOOR UNIT):
Type
Axial
Axial
Quantity
[pcs]
1
1
Voltage/frequency
[V]/[Hz]
230 / 50
230 / 50
Power consumption
[W]
40
68
Max. operating current
[A]
1.40
1.40
EVAPORATOR (OUTDOOR UNIT):
Appliance type
VHS-M 9
VHS-M 14
Dimensions HxWxD
[mm]
1080x1290x960
1080x1290x960
Type
Finned pipe
Finned pipe
Quantity
[pcs]
1
1
Weight
[kg]
93
93
Fin pack material
Copper/aluminium
Copper/aluminium
Casing material
Stainless steel, coated
Stainless steel, coated
Max. refrigerant operating pressure
[bar]
30
30
Relative humidity
[%]
80
80
Heat transfer medium temperature differential
[K]
5.7
5.7
Air flow rate
[m³/h]
3000
4000
Application range min./max
[°C]
-24 / +40
-24 / +40
Sound power level/sound pressure level
[dBA]
52/23
54/26
Sound power level/sound pressure level (in silent mode)
[dBA]
49/20
51/23
i
Information
Data on sound pressure levels refer to operation at
full load at a distance of 10 m (free space). Sound
pressure and sound power levels are given +/-3
dB(A).
i
Information
Silent mode offers four separate time windows
during which the outdoor unit can be operated
with reduced sound levels. It is set via the OTE
controller.
Содержание AIR 7
Страница 2: ......
Страница 91: ...INSTALLATION Declaration of Conformity 982000 AIR M2 M4 EN03 1 www ochsner com 91 16 Declaration of Conformity...
Страница 92: ...INSTALLATION Declaration of Conformity 92 www ochsner com 982000 AIR M2 M4 EN03 1...
Страница 99: ...982000 AIR M2 M4 EN03 1 www ochsner com 99...