INSTALLATION
| Specification
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 67
14.3 Limits of use
Limits of use
AIR 7
AIR 11/AIR 18/AIR 23/AIR 29/AIR 41
Outdoor temperature/max. heat pump flow temperature
A 0 / W 65°C
A -5 / W 60°C
A -15 / W 50°C
A -10 / W 65°C
A -15 / W 60°C
A -20 / W 55°C
Underfloor heating (-15°C / 35°C)
Yes
Yes
Radiators (-15°C / 55°C)
Yes
(size the booster heater for 100%
of the heat load)
Yes
Radiators (-15°C / 65°C)
Yes
(size the booster heater for 100%
of the heat load)
Yes
(size the booster heater for 100% of the heat
load)
Domestic hot water
Yes
Yes
AIR 7
12_04_200_202_01_001 AIR_7
-20 -15 -10
-5
0
5
10
15
40
50
60
20
-23
65
55
Y
X
1
2
X Outdoor temperature [°C]
Y Flow temperature [°C]
1 Flow temperature application limit for heat pump
2
Maximum flow temperature for configuration
AIR 11, AIR 18, AIR 23, AIR 29, AIR 41
12_04_200_202_01_001 AIR_1
1-41
-20 -15 -10
-5
0
5
10
15
40
50
60
20
-23
65
55
Y
X
1
2
X Outdoor temperature [°C]
Y Flow temperature [°C]
1 Flow temperature application limit for heat pump
2
Maximum flow temperature for configuration