49 | EN
Mounting instructions, PYROLINE
®
Con PLC fire protection duct
Mounting PYROLINE® Con S PLC with a support system
8 10
Creating a wall connection
If the fire protection duct is run through the wall, or meets the wall and
only the cables are run through, the wall connection must be designed
according to the mounting situation.
Mounting situation
Mounting version (p. 51–56)
Duct
Classification period of the wall/
ceiling in comparison with the
duct
PYROLINE
®
Con S PLC
Ends in front of solid wall
Equal or higher
D
Less
D
None
Not approved
Passes through solid wall
Equal or higher
E
Less
B
None
C
Ends in front of light-duty partition
Equal, higher, less or none
Not approved
Passes through light-duty partition wall
Equal or higher
F
Less
G
None
C
Tab 7:
Mounting situations, wall connections
PYROLINE
®
Con S PLC wall connection collar
1
1
2
Fig 44:
Overview, PYROLINE
®
Con S PLC wall connection collar
1
Shorter plates of the wall connection collar
2
Longer plates of the wall connection collar