Con PLC fire protection duct
Mounting PYROLINE® Con S PLC with a support system
8 7
Mounting separating retainers
If cables with different functions or voltages are routed in the
PYROLINE
®
Con PLC fire protection duct, they must be separated by
separating retainers to avoid malfunctions or interference.
2
3
1
Fig 41:
Separating retainer mounting
1. Mount the separating retainer
1
on the duct base with the KRS 6x30
screw
3
.
2. Mount additional separating retainers flush with the previous separat-
ing retainer.
3. Attach separating retainer connectors
2
at the joints of the separating
retainer.
8 8
Mounting an end piece
1
2
3
Fig 42:
End piece mounting
The fire protection duct must be tightly closed to prevent smoke gases
from escaping during a cable fire. Open cable ends are closed off with
an end piece suitable for the fire protection duct.
1. Stick the sealing strip on the front side
1
of the previously mounted
duct trough.
2. Mount the end piece
2
in front of the front side with at least 4 coun-
ter-sunk head screws
3
.