Mounting instructions, PYROLINE
®
Con PLC fire protection duct
Mounting PYROLINE® Con D PLC on a wall/ceiling
7 4
Creating a 90° flat angle
Fig 13:
90° flat angle
To run cables on at a 90° angle, it is possible to create 90° flat angles
with the PYROLINE
®
Con D PLC product version. During mounting,
proceed as described in chapter “7.1 Mounting the duct trough” on page
15. The cables must be routed before the duct cover is mounted.
K1
K2
K1
K2
B
C
D
D+3 mm
B
A
C
1
A
2
Fig 14:
90° flat angle duct trough mounting
1. Notch out the inner side section of the duct trough
K1
by dimension A
(duct interior width).
2. Stick sealing strips to the remaining front surface
1
.
3. Mount the duct trough
K1
.
4. On the duct trough
K2
, which is supposed to connect at a 90° angle,
notch out the lower duct wall and duct base by dimensions B (inner
duct width plus a duct wall thickness), C (duct base width minus duct
wall thickness) and D (duct base width) plus 3 mm sealing strip.