35 | EN
Mounting instructions, PYROLINE
®
Con PLC fire protection duct
Mounting PYROLINE® Con D PLC on a wall/ceiling
Mounting version
B
– Uncut duct penetration, wall connection collar on both sides
Note!
The mounting version shown applies in the same way for ceiling penetra-
tions.
1
2
3
max. 2 cm
Fig 28:
Wall connection mounting version
B
1. Create a wall opening for the duct penetration.
Note!
Wall opening max. 2 cm > external duct dimensions.
2. Run the fire protection duct through the wall opening and mount it on
the wall
1
, see also “7.1 Mounting the duct trough” on page 15.
3. Close the ring gap around the duct with MIW-S mineral wool
2
.
4. Seal the mineral wool with non-combustible material, e.g. plaster.
Mount a wall connection collar on both sides of the wall
3
:
5. Mount plates directly on the wall abutting the fire protection duct with
counter-sunk head screws.