Planning an installation
6 3
Approved cables
PYROLINE
®
Con PLC fire protection duct for fire encapsulation
(EI30–EI60, EI90)
All standard cable types up to a maximum diameter of d = 21 mm,
including fibre-optic cables, can always be routed. This excludes hollow
core cables and wire cables.
Note!
When dimensioning the cables, note that the electrical resistance of the
conductors in the cable is increased through heating. A larger conductor
cross-section may be required.
Comply with the maximum approved cable load (see Table 5). The
approved cable load is independent of the fire resistance class and the
dimension of the fire protection ducts:
Duct type
Wall/ceiling mounting
Mounting
with
support
system
Cable load
Cable
directly on
top
Cable mounting
with separating
bracket/separat-
ing clamp
PYROLINE
®
Con D PLC
x
–
–
≤ 10.0 kg/m
PYROLINE
®
Con D PLC
–
x
–
≤ 15.3 kg/m
PYROLINE
®
Con S PLC
–
–
x
≤ 31.5 kg/m
Tab 5:
Maximum approved cable load