![OBO Bettermann EI30 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/obo-bettermann/ei30/ei30_mounting-instructions_3169658045.webp)
45 | EN
Mounting instructions, PYROLINE
®
Con PLC fire protection duct
Mounting PYROLINE® Con S PLC with a support system
1
Fig 38:
Connection of fittings
4. Place the fitting on the bracket or support rail.
Note!
When using a vertical bend and a vertical rising/falling cable
guide, the fire protection duct must be mounted in this area with the
GMS connection bracket on the support rail or the bracket. See also
“8.6.1 Mounting a vertical bend on a bracket or support rail” on page
46.
5. Screw the pre-mounted connectors
1
to the end of the duct trough
and the fitting.
2
Fig 39:
Fittings, duct cover mounting
6. Stick the sealing strip
2
all along the support surface and one front
side of the duct cover.
7. Place the duct cover on the duct trough so that the joint overlap is
located on the following duct trough.