![OBO Bettermann EI30 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/obo-bettermann/ei30/ei30_mounting-instructions_3169658043.webp)
43 | EN
Mounting instructions, PYROLINE
®
Con PLC fire protection duct
Mounting PYROLINE® Con S PLC with a support system
8 5
Mounting the duct cover
Before the duct cover is mounted, all the necessary fittings and separat-
ing retainers must be mounted and the cables routed. Mounting of the
duct cover can deviate when fittings are used, refer to the appropriate
chapters.
1
2
3
4
Fig 36:
Duct cover mounting
1. Stick the sealing strip all along the support surface
3
and one end of
the duct cover
1
.
2. Place the duct cover on the duct trough so that the joint overlap
4
is
located on the following duct trough. It is not necessary to screw it to
the duct trough.
3. Fully close joints to the wall
2
with KTM mortar.
The fire protection duct is fully mounted. The wall connection must be
made according to the mounting situation. See also chapter “8.10 Creat-
ing a wall connection” on page 49.
Содержание EI30
Страница 63: ...EN 63 Notes...