Electrical Data
MOL 3400 & 4100 Modulating and High/Low Burners
Control MCB
is 6 Amp in all cases
Control
Fan
Motor Main
Burner
MCB Size
Fan Motor
MCB Size
Overload
Cable Size
MOL 3400-36
6 Amp
7.5 kW
3 x 20 Amp
11-16 Amp
4mm
2
MOL 3400-41
6 Amp
11.0 kW
3 x 32 Amp
19-27 Amp
6mm
2
MOL 3400-44
6 Amp
15.0 kW
3 x 40 Amp
26-35 Amp
6mm
2
MOL 4100-36
6 Amp
7.5 kW
3 x 20 Amp
11-16 Amp
4mm
2
MOL 4100-41
6 Amp
11.0 kW
3 x 32 Amp
19-27 Amp
6mm
2
MOL 4100-44
6 Amp
15.0 kW
3 x 40 Amp
26-35 Amp
6mm
2
Pumping Unit details for all sizes of burner
Modulating Pump
Motor
Main
Pumping Unit Motor
MCB Size
Overload
Cable Size
1.5 kW x 2800 rpm
6 Amp
2.7 – 4.2 Amp
1.5mm
2
High/Low
Pump Motor
Main
Pumping Unit Motor
MCB Size
Overload
Cable Size
1.1 kW x 1425 rpm
4 Amp
1.8 - 2.8 Amp
1mm
2
MOL 3400-4100 Issue 2 10/08