background image

15 

It is Important that you read the whole Section before proceeding with any Building Work. 
As a Standard suitable Fire Surround is unlikely to be available a Fire Surround will have to be Purpose Made. 
14.1 - FIRE SURROUND or SLIPS REQUIREMENTS -  

REFERENCE SHOULD BE MADE TO THE DIAGRAMS  

a. 

Stone, Slate or Marble Fire Surrounds or Slips and/or any adhesives used must have a 150 Degree Centigrade rating. Care should 

 

be taken with Micro Marbles claiming to have a 150Centigrade Rating as they can suffer from odour, blistering and discolouration. 

 

A Fire Surround consisting of both Combustible and Non Combustible materials can be used, however the following applies: 

   

The  Lower Shelf or Hearth below the fire Must always be Non-Combustible.   

     

The  Upper Shelf or Mantel above the fire can be either Combustible or Non Combustible, however for Combustible it Must be 

 

   positioned 150mm above the Enclosure Opening for shelves up to 150mm deep and raised 25mm for every 25mm of extra depth. 

     

Any side members of the Fire Surround can be either Combustible or Non Combustible, however for Combustible they Must be 

        at least 100mm from the Enclosure Opening for depths of up to 100mm deep and moved a further 25mm for every 25mm of  
        extra  depth.  

 

 

b. 

The Fire Surround design should take account of the preferred height position of the Fire and Enclosure Opening.  

c. 

 If a Wall Mounted Television is being considered then you should also consult Section 15 as this could determine the preferred  

       Height position of the Fire and Enclosure Opening.  

d.   

The Fire Surround Back Panel or Slips must cater for a flat area around the opening to cater for the Trim.

 

      The minimum sizes required for each trim are detailed below. You may wish to also have a border around the outside of the trim. 
      The Flat Area Sizes Required are shown below. Also those with an 100mm border are also shown below. 
                                           Minimum Flat Sizes for Trims                                   100mm Border Plus Minimum Flat Sizes for Trims  
                                        Width (mm)                  Height (mm)                                      Width (mm)                  Height (mm) 
          Harmony Trim         670mm                         425mm                                            870mm                         625mm     
          Deluxe Trim             770mm                         525mm                                            970mm                         725mm                      
          Grande Trim          1025mm                         880mm                                            1225mm                        880mm 
          Concept Trim           770mm                        425mm                                              970mm                         625mm  

e. 

There are no limitations on the depth of  Fire Surrounds Shelf/Mantel, for  

      Non Combustible Shelf/Mantels however where they are deeper than  
      150mm and below the minimum position of 150mm above the Enclosure 
      opening they will reduce the Radiant Heat.  
      It is therefore recommended that Natural Materials are used as some  
      Micro Marbles claiming 150 Centigrade Ratings as they can suffer from  
      odour, blistering and discolouration. 

f. 

Provided the bottom of the Enclosure Opening is at least 250mm above 

      the floor there is no depth requirements for the Fire Surround base/hearth.   

 

g. 

If the height above the floor to the Enclosure Opening is reduced below the 

      minimum of 250mm the depth of the Fire Surround base/hearth must be at  
      a minimum of 150mm depth.  

h. 

The Enclosure must cater for a minimum depth of 330mm as shown. 

i. 

You can recess both the Fire Surround Hearth/Shelf  and Mantel into the 

      wall to provide support, however they must only be let into the wall to the 
      same depth as the Lintels. Lintels must still be used as the Shelf may not 
      provide enough structural support and could crack shortly after Installation 
      or some time in the future if Lintels are not used.

 

j. 

The Fire Surround back panel must be fully sealed to the Enclosure  

      Opening to ensure a good flue seal. 
 
 
 
 

14.2 - WALL COVERINGS 

With any form of heating appliance convection air will rise up past the fire carrying particles of dust that will in time result in varying 
degrees of wall staining. The use of a Fire Surround and or Slips will help to reduce this effect. 

a.    

A

 

Fire Surround will contain the heat and it is therefore preferable to use a Surround Back Panel or Slips to shield the area 

       between the Enclosure Opening and Fire Surround as any Wall Covering may not withstand the temperatures in this area.   

b.   

The fire provides an high heat output so we recommend that any wall coverings are best cut back to the outer edges of the Slips or  

      just within the outer edges of the Fire Surround. 

c.   

Over time some staining might occur and we therefore suggest due consideration is taken when considering the use of patterned  

     paper around the Fire Surround or Slips. 

Due to the heat output of The Icona 600H.E. it is not recommended to use blown vinyl wall covering around the fire. 
 

14.3 - CLEARANCES TO COMBUSTIBLE MATERIALS

 

a.

   Any side members/walls of the Fire Surround can be either Combustible or Non Combustible, however for Combustible they Must  

     be at least 100mm from the Enclosure Opening for depths of up to 100mm deep and moved a further 25mm for every 25mm of  
      extra  depth.  

 

 

b.   

With all heating appliances, soft furnishings, decorations and wall coverings may discolour or scorch if placed too close.

 

c.

  No combustible material, e.g. curtains must be closer than 500mm to the Builders Opening. 

 
 
 

14. - INSTALLATION FOR FIRES WITH TRIMS & FIRE SURROUND 

   

BUILDING ENCLOSURE REQUIREMENTS & FIRE SURROUND REQUIREMENTS 

        If a Wall Mounted Television is being Considered Also Make Reference to Section 18  

Fire Surround Applications for 
Icona 600HE with Trims 

Содержание The Icona 600 H.E.

Страница 1: ......

Страница 2: ...ilders Enclosure Fire Surround Requirements 15 Installation for Trimless Fires Fire Surrounds 18 Builders Enclosure Fire Surround Requirements 16 Installation for Fires with Trim into False Chimney Breasts 21 Flue Hole in the Wall Builders Enclosure Requirements 17 Installation for Trimless Fires into False Chimney Breasts 25 Builders Enclosure Flue Fire Surround Requirements 18 Installation Requi...

Страница 3: ...ishes Sizes Grande trim will have 4 additional Magnets 1 2 100mm length of 6mm x 4mm self adhesive silicone sealing strip 1 10mm Back Nut olive to connect 8mm copper pipe gas supply to the burner via the isolation elbow 1 Chosen Rear Liner Pack Matt Black Light Board or Slate Wall Effects 1 Chosen Trim Assembly Harmony Deluxe Grande or Concept No Trim required for Trimless Models 1 Fuel Effect Set...

Страница 4: ...e no user replaceable parts in the appliance apart from the batteries for the Thermatronic Radio Frequency Electronic Control System p The Batteries may need to be changed every 6months dependant on usage of the fire q If any modifications are made to the property e g double glazing addition of extraction fans or anything that could affect ventilation then the Installer should be contacted to have...

Страница 5: ......

Страница 6: ...the left side of the fire see Section 2 2 f e In the event that the fire shuts down due to any reason attempt to restart it If there is a continuing problem call in a properly qualified specialist engineer f The Matrix pieces in the fire are Moulded Ceramic Fibre components incorporating Silicone Binders and you may notice that they develops cracks during operation This is natural shrinkage caused...

Страница 7: ...e the Installer Liable to Prosecution and Invalidate the Warranty IMPORTANT BEFORE PROCEEDING WITH THE INSTALLATION READ THESE INSTRUCTIONS CAREFULLY THESE INSTRUCTIONS SHOULD BE LEFT WITH THE USER FOR SAFE KEEPING AND FUTURE SERVICING PRIOR TO INSTALLATION ENSURE THAT THE GAS TYPE AND PRESSURE ARE AS STATED ON THE APPLIANCE DATA BADGE 6 APPLIANCE DATA a Gas Type See Data Plate Natural Gas at 20mb...

Страница 8: ... as a Class 1 Flue ensure the walls are dry lined over the route of the flue and no dabs or battens are in direct contact with the flue blocks otherwise wall cracking will occur as detailed in BS 5440 Pt 1 2008 h A Purpose Designed Flue Box to BS715 fitted with a 125mm 5 twin walled flue with a minimum effect height of 3 meters to BS EN 1856 Details are available from your authorised supplier i En...

Страница 9: ... debris in the gas system can block the valve and gas injectors on this appliance and faults caused by this are not covered by the guarantee Therefore it is important that all gas pipes must be purged of both air and debris j If you suspect that there may still be dirt and or debris in the gas system fit a filter in the pipeline before the gas isolation pressure test elbow k Do not use jointing co...

Страница 10: ...mm to the Builders Opening Note If a shelf is placed to close to the trim or opening it may have an adverse effect on the Trim Finish 12 3 HOLE IN THE WALL BUILDING ENCLOSURE AND OPENING SIZES FOR FIRES WITH TRIMS REFERENCE SHOULD BE MADE TO THE DIAGRAMS BUILDING ENCLOSURE and LINTEL SIZES a It is recommended that a qualified builder constructs the building enclosure b It is recommended that linte...

Страница 11: ...any air gaps between the back of the plasterboard and wall are sealed around the Builders Opening or Fireplace as this can affect flue pull and wall staining see i 12 4 FIXING THE FIREBOX SUPPORT BRACKET ASSEMBLY We Recommend the use of the Firebox Support Bracket as it is provided to cater for the weight of the Fire when fully In stalled with the Burner Box Assembly and Flue Hood or the Flue Cano...

Страница 12: ...ut out to cover the fire and flanges and provide the Trimless Style a It is recommended that a qualified builder constructs the building enclosure b It is recommended that lintels are used as detailed in the diagrams above structural checks may be required The diagrams show the maximum sizes of Lintel depth that can be used c The Building Enclosure must be constructed of Non combustible materials ...

Страница 13: ......

Страница 14: ......

Страница 15: ...g 150 Centigrade Ratings as they can suffer from odour blistering and discolouration f Provided the bottom of the Enclosure Opening is at least 250mm above the floor there is no depth requirements for the Fire Surround base hearth g If the height above the floor to the Enclosure Opening is reduced below the minimum of 250mm the depth of the Fire Surround base hearth must be at a minimum of 150mm d...

Страница 16: ...rovision for a gas supply as detailed in Section 11 during construction of the Enclosure n If plaster board is used to face off the Building Enclosure and it is dry lined to the wall fixed with plaster dabs then the air gap between the Plaster Board and the Wall must be sealed off around the cut out Do not use a foam sealants as this will flow up the gap sealing off the important insulating air ga...

Страница 17: ... the Fire Surround base hearth f If the height above the floor to the Enclosure Opening is reduced below the minimum of 250mm the depth of the Fire Surround base hearth must be at a minimum of 150mm depth and must be Non Combustible g The Fire Surround back panel after the Enclosure has been plastered but must be fully sealed to the Enclosure Opening to ensure a good flue seal 15 2 WALL COVERINGS ...

Страница 18: ...roposed opening or 555mm measured from the base of the proposed opening to cater for the Hood or Canopy k A fully sealed Building Enclosure Must be formed with good mortar joints to ensure the best flue draw is achieved l A flat area will have to be provided around the Building Enclosure to ensure the flanges of the Firebox can be sealed see diagram m The opening sizes in the Enclosure and Fire Su...

Страница 19: ......

Страница 20: ......

Страница 21: ...sed but the plaster board must be left off to the side or where possible to allow for connection of the Flue System a All Wall Coverings or Combustible Cladding Must be removed from the wall where the False Chimney Breast will be sited b It is recommended that a qualified person constructs the building enclosure c The Building Enclosure should be constructed with Studding and Must be lined with 12...

Страница 22: ...ack panel must be fully sealed to the Enclosure Opening after plastering to ensure a good flue seal and have opening sizes as detailed in j o There are no limitations on the depth of Fire Surrounds Shelf Mantel for Non Combustible Shelf Mantels however where they are deeper than 150mm and below the minimum position of 150mm above the Enclosure opening they will reduce the Radiant Heat It is theref...

Страница 23: ......

Страница 24: ......

Страница 25: ...to close to the trim or opening it may have an adverse effect on the Trim Finish 17 3 FALSE CHIMNEY BREAST ENCLOSURE CONSTRUCTION REFERENCE SHOULD BE MADE TO THE DIAGRAMS FALSE CHIMNEY BREAST ENCLOSURE Very Important The False Chimney Breast Studding Structure should be constructed to surround the Enclosure Opening but the plaster board Must be left off to allow for connection of the Flue System a...

Страница 26: ...e Upper Shelf Top Sides and Hearth Base of the Fire Surround can be within 15mm of the Enclosure Opening q We recommend that the False Chimney Breast is ventilated at both top and bottom to keep the structure cool r If the Fire Surround back panel is to be used to provide the correct sized front opening see j then the Enclosure and False Chimney Breast will have to be finished and plastered howeve...

Страница 27: ......

Страница 28: ......

Страница 29: ... Manufactures requirements and spaces the Television at least 35mm away from the Chimney Breast f After reading the Installation Requirements you should compare this with the preferred height position of the Television 18 2 TELEVISION INSTALLATION REQUIREMENTS FOR FIRES WITH TRIMS Providing the Chimney Breast temperatures have been confirmed as detailed in the General Section testing of the Icona ...

Страница 30: ...e a Non Combustible Shelf Fire Surround Mantel that is positioned 15mm above the Enclosure Opening bottom edge of the Television must be at least 200mm above the shelf see diagram e The Television can be Mounted Vertically if desired with a suitable Wall Bracket that spaces the back of the television at least 35mm from the Chimney Breast Wall f To help provide the preferred viewing position a 15º ...

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ...t high The fire should continue to clear its combustion products Also operate any other flued appliance in the same or neighbour ing rooms and ensure they continue to function satisfactorily as multiple flues can work against one another d If spillage is detected during this procedure remove the restrictor see below if fitted and repeat the tests Removing the Restrictor To remove the Restrictor fi...

Страница 46: ... if the fire is to be used in the presence of young children the elderly the infirm and pets 23 SERVICING The Matrix Pieces in the fire are Moulded Ceramic Fibre component incorporating Silicone Binders and you may notice that they de velop cracks during operation This is natural shrinkage caused by exposure to high temperatures and is quite normal for the material and will in no way affect the op...

Страница 47: ...a Prior to carrying out any of the following steps ensure that you have carried out the procedures in Section 23 1 General Servicing to the appropriate level as required b Check the supply pressure at the isolation elbow c Important With the Thermatronic RF System always change the batteries before carrying out any Fault Finding It is important to know the ignition sequence prior to conducting any...

Страница 48: ... injector Check the Burner Pressure are as detailed in Section 6 Appliance Data Ensure the test point is sealed off after checking Check and change the main injector as required c Check that another appliance is not affecting the gas supply pressure d Check there is not a flue ventilation problem carry out a spillage test e Check fuel bed layout as detailed in Section 20 24 8 FIRE OPERATES FOR A W...

Страница 49: ......

Страница 50: ...y to us We will not be liable for any such breakages or losses Under no circumstances should any attempt be made to repair the burner on site without our express knowledge and approval during the warranty period This guarantee is given subject to the following provisions 1 That the installation is carried out by a GAS SAFE registered installer we may require their registration details 2 That the a...

Отзывы: