12
It is Important that you read the whole Section before proceeding with any Building Work.
13.1 - WALL COVERINGS
With any form of heating appliance convection air will rise up past the fire carrying particles of dust that will in time result in
varying degrees of wall staining.
Over time some staining might occur and we therefore suggest due consideration is taken when considering the use of patterned
paper around the fire.
Due to the heat output of The Icona 600H.E. it is not recommended to use blown vinyl wall covering around the fire.
13.2 - CLEARANCES TO SHELVES & COMBUSTIBLE MATERIALS
a.
A 150mm
non combustible
shelf can be fitted above the fire but must be positioned at least 15mm above the Enclosure
Opening. For deeper shelves they must be raised a further 25mm for every extra 25mm of depth.
b.
A 150mm
combustible
shelf can be fitted above the fire but must be positioned at least 150mm above the Enclosure Opening.
For deeper shelves they must be raised a further 25mm for every extra 25mm of depth.
c.
Any combustible sidewall must be at least 275mm from the inside of the Enclosure Opening.
d.
With all heating appliances, soft furnishings, decorations and wall coverings may discolour or scorch if placed too close.
e.
No combustible material, e.g. curtains must be closer than 500mm to the Enclosure Opening.
13.3 - HOLE IN THE WALL BUILDING ENCLOSURE AND OPENING SIZES FOR TRIMLESS FIRES
REFERENCE SHOULD BE MADE TO THE DIAGRAMS
BUILDING ENCLOSURE, LINTEL SIZES and FLAT AREA REQUIREMENTS
Important : The Building Enclosure will have to be constructed first allowing for the fire to be built-in prior to the front face,
i.e. Plaster Board being cut out to cover the fire and flanges and provide the Trimless Style.
a.
It is recommended that a qualified builder constructs the
building enclosure.
b.
It is recommended that lintels are used as detailed in the diagrams
above, structural checks may be required.
The diagrams show the maximum sizes of Lintel depth that can be used.
c.
The Building Enclosure must be constructed of Non-combustible materials.
d.
No Combustible materials must be present in the Enclosure.
e.
First determine the preferred bottom position of the Enclosure
Opening, we recommend 500mm but the minimum is 250mm.
f.
If a Wall Mounted Television is being considered then you should
also consult Section 18 as this could determine the preferred
Height position of the Fire and Enclosure Opening.
g.
The inner Base of the Building Enclosure Must be at least 180mm
below the bottom of the Enclosure Opening to cater for the
sunken Burner System.
h.
The Builders Enclosure must be at least 580mm wide to cater for
the Firebox, Burner Box System and Flue Hood or Canopy.
i.
The Enclosure must cater for a minimum depth of 330mm as shown.
j.
A fully sealed Building Enclosure Must be formed with good mortar
joints to ensure the best flue draw is achieved.
k.
A flat area will have to be provided around the Building Enclosure to ensure the
flanges of the Firebox can be sealed.
l.
The Building enclosure should have provision for a gas supply as detailed in Section 11 during construction of the Enclosure.
IMPORTANT: The Firebox will now have to be Built-in to the Building Enclosure before the outer plaster board face is
applied See 13.5
13. - INSTALLATION FOR TRIMLESS FIRES
(Showing Lintel & Shelf Details)
BUILDERS ENCLOSURE REQUIREMENTS & FITTING THE FIREBOX
The Optional Edge Kit Provides A Frame For Plastering Up To
If a Wall Mounted Television is being Considered Also Make Reference to Section 18
Содержание The Icona 600 H.E.
Страница 1: ......
Страница 5: ......
Страница 13: ......
Страница 14: ......
Страница 19: ......
Страница 20: ......
Страница 23: ......
Страница 24: ......
Страница 27: ......
Страница 28: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 49: ......