8-7
(b) ‘OFF area’ [limit switch ‘open (b) contact’ operation] dog position writing:
The numerical pairs used to write the ON position data are larger than those used to write the
OFF position data. If the numerical values for each dog are not written in order, beginning from
the lowest and proceeding to the highest, error ‘31’ will be activated.
(3) The ‘number of multi-dogs’ setting range is as follows:
If a setting of ‘0’ is designated, the dog ON/OFF position data at that channel will be inoperative.
Any setting exceeding ‘10’ will be processed as ‘10’.
(4) The setting range for the ON/OFF position data (scaling binary values) is as follows:
[Minimum current position value] to [Minimum current position value + scale length –1]
Содержание Varlimit VS-212DN
Страница 1: ...U S E R S MAN U AL V S 2 1 2 DN NSP Z2004 7...
Страница 2: ......
Страница 47: ...5 1 5 Operations 5 1 Operating Sequence Flowchart An operation flowchart is shown below...
Страница 52: ...6 2 6 1 Pre Operation Setting Sequence...
Страница 64: ...6 14...
Страница 66: ...6 16...
Страница 90: ...7 22...
Страница 94: ...8 3 8 1 Pre Operation Setting Sequence This section explains the setting sequence for the limit switch function...
Страница 102: ...8 11...
Страница 104: ...8 13...
Страница 105: ...8 14...
Страница 106: ...8 15...
Страница 109: ...8 18...
Страница 110: ...8 19...
Страница 111: ...8 20...
Страница 113: ...8 22...
Страница 114: ...8 23...
Страница 115: ...8 24...
Страница 121: ...10 1 10 DIMENSIONS 10 1 VS 212DN Units mm...
Страница 124: ...10 4 10 4 ABSOCODER sensor Units mm...
Страница 125: ...10 5 Units mm...
Страница 126: ...10 6 10 5 Extension Cable 1 4P S 0102 L 4P RBT 0102 L Units mm...
Страница 128: ......
Страница 129: ......
Страница 130: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......