NSC Sicherheitstechnik GmbH
45/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
Functional tests
Test
Measured value
Test result
Normal operation
- green LED „Operation" lights
- green LED „Night“ lights
Ο
ok.
Ο
fault
Fire condition
- Test of all automatic detectors
- Test of all manual call points
The fire condition can be generated in the installer
level by functions "testalarm“ or "simulation“.
Check display at FCP, remote panels and printer
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault
Fault condition
- loop
- power outputs
- monitored inputs
- RS485 bus
- battery
- mains fault (mains fault delay)
Check display at FCP, remote panels and printer
..........
Min
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault
Ο
o.k.
Ο
fault
Ο
o.k.
Ο
fault
Ο
o.k.
Ο
fault
Disabled condition
- detector
- zone
- power output
Check display at FCP, remote panels and printer
Ο
o.k.
Ο
fault
Ο
o.k.
Ο
fault
Ο
o.k.
Ο
fault
Alarm devices
- transmission device activation
- flash lights
- sounders
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault
Fire outputs
- relays
- outputs
- output modules
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault
Current of FCP at mains fault
Required bridge over time
Required battery capacity
...............mA
………….h
…………Ah
Ο
ok.
Ο
fault
Ο
ok.
Ο
fault