NSC Sicherheitstechnik GmbH
27/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
26
Revision Status
from zone : 2 Normal
to zone : 4 Normal
Cancel On Off
Menu „Revision“
The revision mode can be used to check the
detectors by detector test equipment (e.g. Solo test
equipment). When the detector is activated by the test
equipment the alarm is displayed at the FCP and
reset automatically if analogue value falls below the
alarm threshold.
Please type in the number of zones which shall be
investigated by the revision mode. Every line has to
be confirmed by “OK“.
Please activated the revision mode for the selected
zones by F2 („on“). Pay attention: the zones in
revision will be displayed at the panel as „disabled“.
The alarm of such a zone will be displayed in the LC
module as „T E S T A L A R M“
After finishing the revision do not forget to switch
off the revision mode by F3 („Off“) because an
alarm of these zones will not be transmitted to the
fire brigade.
The Apollo DISCOVERY sounder will be set in
configurstion mode by setting the group to revision.
This enables the functions to switch it on / off and
change volume setting by the magnetic wand.
After switching the revision off you cann accept or
discard the volume change of each sounder.
27
Settings 1
1. Date/Time 5. Delete program
2. System settings 6. Delete texts
3. Scan RS485 7. Delete Events
4. Scan detectors 8. Language
zurück mehr Enter
Settings 1 of FCP
1. To change date, time and day of the week
Jump to Menu
28
2. To enter sub menu for system settings
where some individual hardware and
software features can be configured
Jump to Menu
29
3. After pressing 3. LCD repeater panels
connected to serial interfaces will be
scanned. The number of found devices will
be displayed in the last but one display line
Jump to Menu
30
4. To enter sub menu for new scanning of
addressable detectors
Jump to Menu
31
5. To delete configuration of FCP. Before
deleting there will be a security inquiry
Jump to Menu
32
6. To delete detector texts. Before deleting
there will be a security inquiry
Jump to
Menu
33
7. To delete all events in event memory. Before
deleting there will be a security inquiry
Jump to Menu
34
8. To change the panel’s language
Jump to
Menu
35
For another settings menu please press F3 („more“)
to enter sub menu „Settings 2“
Jump to Menu
36
28
Date/Time
Day : 09 Friday
Month : 07 Winter
To set date and time
Please type the right data line by line and confirm
every line by OK.