NSC Sicherheitstechnik GmbH
14/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
marked with "-" this message will not be displayed.
You can switch from "x“ to "-“ by push button F3
(“off”) and from “-“ to “x” by push button F2 (“on”).
The example on the left side shows only alarm and
pre alarm messages but all other kind of message
are hidden.
06.2
Event memory
from message :
to message :
Cancel print
Event memory: "Printing“
Please type the number of messages and confirm
every line by "OK“: The last (youngest) message is
message no. 1 and the oldest one is message no.
1034.
After selecting the messages press F4 ("print“) for
printing.
The print goes out through the interface which is
selected by menu "Settings 2“ -> "2. Interfaces“ ->
"Protocol" -> "Printer".
07
Zone | existing | config.
> 0001 | 010 | 010
0002 | 010 | 010
0003 | 011 | 107
0004 | 003 | 127
0005 | 010 | 010
0006 | 021 | 117
Cancel Segment Details
Segment | existing | Current
> 01 | 024 | 008,4mA
02 | 031 | 010,9mA
| |
| |
| |
| |
Cancel Zone Details
Detector data
Here the zones which contain at least one detector
are listed line by line (left column).
The middle column shows the number of detectors
which were found during last loop scanning.
The right column "config.“ shows the number of
detectors which were configured by configuration
software.
Ideally the numbers in the middle and right
columns should be identical.
By pressing key F3 "Segment", the display will
change to a list of segments with number of
connected devices and current on each segment.
Please select with the cursor keys the zone/segment
which should be investigated more detailed and press
„Details“ (F4)
Jump to Menu
07.1
07.1
Zone 0003 Detect. 002/010
No. |Type |Seg.|Add|Status
001|Conv. mo. CHQ_MZ|01:o|001|Normal
>002|Flashl. CHQ_AB|01:o|002|Normal
003|Ion. det. AIE_E |01:o|003|Normal
004|opt. det. ALG_E |01:o|004|Normal
005|Conv. mo. CHQ_Z |01:o|005|Normal
Cancel existing Details
Table of detectors
The first line of the LC module shows zone and
number of the detector which is marked by ">“ in the
left column of the display area. Here in this example it
is zone 0003 and detector 002 of 10 detectors in
this zone at all.
The second column shows all configured detectors of
this zone by name (abbreviated), doesn’t matter if
they are connected to the panel or not. If you want to
see only the connected detectors of this zone press
"existing“ (F2).
In this case the bottom line changes and "config.“ is
written above F2. Additionally the number of
detectors in line 1 will change, if there is a difference
between connected and configured detectors for this
zone.
Pressing F2 again will show all configured detectors
again.
One detector is shown per line. The grey line have the
following meanings :