NSC Sicherheitstechnik GmbH
5/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
1. Description of Control Panel:
Picture of the control panel of the "Solution F2":
LED indications
Dynamic functions keys F1 – F4,
Keypad and cursor push buttons
The functions are individually indicated
in the bottom line of the LC module
Field programmable push buttons S1 – S2
‘Prog’ : to select the main menu
‘ext. sounders off / on’
‘int. buzzer off“ / “LED test’
‘Reset’
LED indications:
LED :
Description :
green LED "In Operation“
The Fire Control Panel (FCP) is in operation.
green LED "Delay“
Delay of transmission device signal to the fire brigade for
automatic detectors.
green LED "No Delay“
Indicates that the FCP is in normal operation mode. That
means the main alarm is NOT delayed and any alarm
activates the Fire Brigade immediately.
green LED "Service“
Indicates that the FCP is in „Service Mode“.
red LED "Main alarm“
Indicates that the FCP is in Alarm condition. See LC
module for detailed information. If an alarm transmission
device (TD) is connected to the panel the panel has tried
to activate the TD.
red LED "Internal alarm“
Indicates that the FCP is in Alarm condition. See LC
module for detailed information.
red LED "Fire Brigade alarmed“
Indicates that the FCP has activated the alarm
transmission device (TD) to the Fire Brigade and the TD