NSC Sicherheitstechnik GmbH
31/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
6. Opens input screen to unlock possible
options
Menu
43
By pressing Cancel(F1) you get back to menu
Settings 1
jump to Menu
27
37
Installer
old access code: 00000
new access code: 22351
new access code: 22351
Cancel
Changing the installer access code
First you have to type the old access code, then you
have to type two times the new access code.
Every line has to be confirmed with „OK“.
Example left side : old access code 00000 is replaced
by new access code 22351.
38
Interfaces
1. UART 1
2. UART 2
3. UART 3
Cancel Protocol Baud rate
Configuring the interfaces
The FCP offers 3 different serial interfaces RS-232
(see wiring diagrams). UART 3 only is available, if the
RS485 extension module is mounted.
For every interface a certain protocol can be
configured e.g. for printer, PC configuration etc. This
means the FCP is easily to adapt to the required
application and very flexible.
Please select UART 1, 2 or 3 by the cursor keys
↑
,
↓
and then press F2 („Protocol“)
Jump to Menu
38.1
After that you can configure the “baud rate” by
pressing F3
Jump to Menu
38.2
38.1
Interfaces UART 1
1. Printer 5. Modbus PLC
2. FRP
3. PC
x
4. ESPA 4.4.4
Cancel On save
Interface protocols
The example on the left side shows UART 1.
Please select the protocol you want to assign to
UART 1 by using the cursor keys. The following
protocols are available :
Printer
FRP (Fire Brigade Repeater Panel)
PC configuration (Laptop)
ESPA 4.4.4 (Option)
Modbus PLC
After selecting the protocol it has to be activated by
pressing On (F2). The activation will be indicated in
the 1
st
display line.
By pressing Off (F3) the protocol will be deactivated
again.
Press save (F4) to save the new configuration.
38.2
Interfaces UART 1
1. 4800 5. 57600
2. 9600 x 6. 115200
3. 19200 7. 1200
4. 38400 8. 2400
Cancel Off save
Interface baudrates
The example on the left side selects baudrate of 9600
of UART 1.
After selecting the baudrate it has to be activated by
pressing On (F2). The activation will be indicated in
the 1
st
display line.
By pressing Off (F3) the protocol will be deactivated