Installation
Nortec EL
2582302_C_EN_1611
Figure 19:
A
A
B
C
E
D
Installation Example – Remote-Mounted Blower Pack
A Steam line must run minimum 12 in (300 mm) vertically before continuing on to the blower pack.
B All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the blower pack.
C The steam line must not exceed the length specified in
Table 6 on page 28
. The minimum bend radius is 12 in (300 mm) for a steam
hose, or 5× the internal diameter for rigid steam pipes.
D All condensate traps must have a minimum height of 8 in (200 mm).
E Steam line must have upslope (minimum 10°) /downslope (minimum 2°), and condensate line must constant minimum downslope of
1 in/48 in (1.2°).