31
Installation
Nortec EL
2582302_C_EN_1611
Figure 17:
B
D
D
C
F
A
A
B
B
C
D
C
E
Installation Example – Steam Distributor Less Than 20 in (500 mm) Above Humidifier
A Steam line must run minimum 12 in (300 mm) vertically before continuing on to the steam distributor.
B All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the steam distributor or the steam line.
C The steam line must not exceed the length specified in
Table 6 on page 28
. The minimum bend radius is 12 in (300 mm) for a steam
hose, or 5× the internal diameter for rigid steam pipes.
D All condensate traps must have a minimum height of 8 in (200 mm).
E Obstacle
F Condensate line must connect into a full-size "T" connector installed at the lowest point in the steam line.