24
Installation
2582302_C_EN_1611
Nortec EL
5.4.5 Mounting Checklist
Check the following to ensure that the humidifier has been mounted correctly:
Unit installed in the correct location (according to
"Location and Clearances" on page 16
)?
Mounting surface stable, and capable of supporting the full operating weight of the humidifier?
Unit level?
Unit fastened securely?
5.5
Steam Line Connections
Steam generated by the Nortec EL humidifier is not pressurized, but is delivered at atmospheric pressure.
It can be distributed directly into a conditioned space with a built-on or remote-mounted blower pack, or into
an AHU (air handling unit) using Nortec steam distributors or Nortec SAM-e steam distribution manifold.
Read
"Best Practices for Installing Steam and Condensate Lines" on page 26
before installing steam lines.
5.5.1 Steam Distribution Using the Air Handling Unit
For placement of the steam distributor or SAM-e steam distribution manifold in the air handling unit, as
well as best practices and installation procedures, refer to their installation manuals.
5.5.2 Steam Distribution Using the Blower Pack
5.5.2.1
Placement of Humidifier
Figure 13 on page 25
and
Table 5
show the minimum clearances required for installation of a
Nortec EL steam humidifier with a built-on Nortec blower pack.
Table 5: Minimum Clearances
Blower Pack
Capacity
5 lb/h
(2.3 kg/h)
10 lb/h
(4.5 kg/h)
20 lb/h
(9 kg/h)
30 lb/h
(13.6 kg/h)
50 lb/h
(22.7 kg/h)
75 lb/h
(34.0 kg/h)
100 lb/h
(45.4 kg/h)
Low Speed
Dimension "A" (minimum), Low speed
9 in
(0.23 m)
18 in
(0.46 m)
75 in
(1.91 m)
86 in
(2.19 m)
174 in
(4.42 m)
189 in
(4.81 m)
248 in
(6.3 m)
Dimension "B" (minimum), Low speed
12 in
(0.31 m)
48 in
(1.22 m)
84 in
(2.14 m)
High Speed
Dimension "A" (minimum), High speed
6 in
(0.16 m)
60 in
(1.53 m)
71 in
(1.81 m)
132 in
(3.36 in)
153 in
(3.89 m)
218 in
(5.54 m)
Dimension "B" (minimum), High speed
12 in
(0.31 m)
Dimension "C" (minimum)
90 in
(2.3 m)
Dimension "D" (suggested)
12 in
(0.31 m)
30 in
(0.77 m)
Note:
The values in
Table 5
are based on the following nominal conditions: 72°F (22˚C), 40% RH.
Blower pack should not be installed near cold surfaces or where dew point may be reached.
Higher humidity or lower room temperature (compared to nominal conditions stated above) will require increased clearances.