Installation
2582302_C_EN_1611
Nortec EL
Figure 18:
B
D
C
A
E
Installation Example – Rigid Steam Pipe With Insulation
A Steam line must run minimum 12 in (300 mm) vertically before continuing on to the steam distributor.
B All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the steam distributor, and condensate lines
must have a constant minimum downslope of 1 in/48 in (1.2°).
C The steam line must not exceed the length specified in
Table 6 on page 28
. The minimum bend radius is 12 in (300 mm) for a steam
hose, or 5× the internal diameter for rigid steam pipes.
D All condensate traps must have a minimum height of 8 in (200 mm).
E Steam line must have a minimum of 1 in (25 mm) of pipe insulation over its entire length.