Nortec EL
B.1.2 Performance Checklist
Complete the performance tests after inspecting the site services and the installation, then fill out the form be
-
low.
Note:
When filling out the form leave the checkbox un-checked if the item does not apply, or if the require
-
ment is not satisfied. Enter all notes and exceptions in the space provided
on page vii
.
Distribution System
Note:
For commissioning the distribution system itself, refer
to the individual commissioning checklist for the distribution
system.
SAM-e
Mini-SAM-e
Blower Pack
ASD/BSD/CSD
Model:
Number of XSD units:
Distance to obstruction:
(Minimum 1× absorption distance required from the
distributor to first obstruction (coil/bend ) downstream).
Distance to filter:
(Minimum distance between the distributor and filter
downstream – 1.5-2× absorption distance for class C
filter, and 2.5-3× absorption distance for sub-micron
particle filter).
Preliminary
Pre-start-up checklist completed:
Gas leakage test inside unit completed:
Check for water leaks inside unit com
-
pleted:
Steam cylinder seated properly in its
base:
Condensate trap inside the unit primed:
(Nortec GS CS/NX models only).
All access panels installed and fastened
securely:
Start-Up
Shutoff valve in water supply line open:
Fill tests completed successfully:
Ignition safety shutoff test completed
successfully:
Manual gas shutoff valve open:
On/Off switch set to the On position:
Software version:
Controls
Select the type of signal input connected
to the channels of the low voltage termi
-
nal strip #1:
(Enter setpoint value (if applicable) in the field below
the checkbox).
Demand Humidistat
(modulating)
On/Off Humidistat
Transducer
(modulating)
Digital Controls
CH 1:
CH 2:
On/Off:
If a second set of inputs is connected to
the channels of the low voltage terminal
strip #2 (on dual cylinder units running in
independent mode only), select the type
of signal input connected to the terminal
strip #2:
(Enter setpoint value (if applicable) in the field below
the checkbox).
Demand Humidistat
(modulating)
On/Off Humidistat
Transducer
(modulating)
Digital Controls
CH 1:
CH 2:
On/Off:
Control signal configuration in the soft
-
ware matches inputs connected to unit: