5.1.8 Information
BU 0700 EN
Subject to technical alterations
97
Parameter
Setting value / Description / Note
Available with option
P706
.. - 01
...
.. - 05
Parameter set last error 1...5
always visible
0 ... 3
This parameter stores the parameter set code that was active when the error occurred. Data for the
previous 5 faults are stored.
The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.
P707
.. - 01
.. - 02
Software version
always visible
0 ... 9999
Contains the software status of the frequency inverter and
cannot be changed.
... - 01 =
Version number (3.0)
... - 02 =
Revision number (0)
P708
State of digital inputs
always visible
00 ... 3F
(hexadecimal)
Displays the status of the digital inputs in hexadecimal code. This display can be used to check the
input signals.
Bit 0 = Digital input 1
Bit 1
=
Digital input 2
Bit 2
=
Digital input 3
Bit 3
=
Digital input 4
Bit 4
=
Digital input 5
Bit 5
=
Digital input 6
Bit 6 = Digital input 7 (only with PosiCon)
Bit 7 = Digital input 8 (only with PosiCon)
Bit 8 = Digital input 9 (only with PosiCon)
Bit 9 = Digital input 10 (only with PosiCon)
Bit 10 = Digital input 11 (only with PosiCon)
Bit 11 = Digital input 12 (only with PosiCon)
Bit 12 = Digital input 13 (only with encoder)
ControlBox:
If just four digital inputs are present, then the status is displayed in binary. If the
Customer Unit Multi I/O, Encoder or
PosiCon
is installed (Bit 4, 5 ...), the display is coded in
hexadecimal.
P709
Voltage analog input 1
BSC
STD
MLT
-10.0 ... 10.0 V
Displays the measured analog input value 1. (-10,0 ... 10.0V)
P710
Voltage analog output 1
STD
MLT
0.0 ... 10.0V
Displays the delivered value of analog output 1. (0,0 ... 10.0V)
P711
State of relays
always visible
00 ... 11 (binary)
Displays the actual status of the signal relays.
Bit 0 = Relay 1
Bit 1 = Relay 2
Bit 2 = Relay 3 (Option PosiCon)
Bit 3 = Relay 4 (Option PosiCon)
P712
Voltage analog input 2
MLT
-10.0 ... 10.0 V
Displays the measured analog input value 2. (-10,0 ... 10.0V)
P713
Voltage analog output 2
MLT
0.0 ... 10.0V
Displays the delivered value of analog output 2. (0,0 ... 10.0V)
P714
Opetaring time
always visible
0.0 ... 9999.1 h
Time that the FI has voltage applied and is operational.
P715
Running time
always visible
0.0 ... 9999.1 h
Time during which the FI was enabled.
P716
Current frequency
always visible
-400 ... 400.0 Hz
Displays the actual output frequency.