2 Assembly and installation
BU 0700 EN
Subject to technical alterations
13
2.6 Output choke (accessories)
To reduce interference signals from the motor cable or to
compensate for cable capacitance in long motor cables, an
additional output choke can be installed into the inverter
output.
Take care during installation that the pulse frequency of the
frequency inverter is set to 3-6kHz (P504 = 3-6).
These chokes are specified for a maximum supply voltage of
460V at 0-100 Hz.
An output choke should be fitted for cable lengths over
150m/50m (unshielded/shielded). Further details can be found
in Chapter 2.10.4 "Motor cable".
The protection class of the chokes is IP00 and they must
therefore be installed in a control cabinet.
Inverter type
NORDAC
SK 700E
Output choke 3 x 380 - 460V
Length
L1
Width
B1
Depth
T
Detail: mounting
Conne
c
tion
Type
Permanent
current
Inductance
Length
L2
Width
B2
Mount
ing
1.5 kW
SK CO1-460/4-C
4 A
3 x 3.5 mH
104
125
140
75
84
M6
4
2.2 ... 4.0 kW
SK CO1-460/9-C
9.5 A
3 x 2.5 mH
105
155
160 71.5 130 M6 4
5.5 ... 7.5 kW
SK CO1-460/17-C
17 A
3 x 1.2 mH
97
190
180 96 170 M6 10
11 ... 15 kW
SK CO1-460/33-C
33 A
3 x 0.6 mH
107
190
180
126 170 M6 10
18 ... 30 kW
SK CO1-460/60-C
60 A
3 x 0.33 mH
140
230
290
95 176
M6 35
37 ... 45 kW
SK CO1-460/90-C
90 A
3 x 0.22 mH
140
300
315
94 224
M8 35
55 ... 90 kW SK CO1-460/170-C
170 A
3 x 0.13 mH
185
360
452
145
120
M10
95
110 … 132 kW SK CO1-460/240-C
240 A
3 x 0.07 mH
215
360
472
175
120
M10
150
160 kW SK CO1-460/330-C
330 A
3 x 0.03 mH
200
300
270
145
240
M8
CU bar
bolts
All dimensions in [mm]
[mm
2
]
T
B2
B1
L1
L2
1
3
4
2
5
6