
5.1.6 Fehler! Verweisquelle konnte nicht gefunden werden.
BU 0700 EN
Subject to technical alterations
89
Parameter
Setting value / Description / Note
Available with option
P509
Interface
always visible
0 ... 21
[ 0 ]
Selection of the interface via which the FI is controlled. (P503: Note
Master function output
!)
0 = Control terminals or keyboard control
**/*** with the
Control Box
(Option), the
Parameter Box
(Option, not
ext. p-box
), the
Potentiometer Box
(Option) or via
Bus I/O Bits
(Option)
1 = Control terminals only */***,
the FI can only be controlled via the digital and analog inputs (
Æ
a
customer unit is necessary!) or via the
BUS I/O Bits
(Option).
2 = USS setpoint */***
, the frequency setpoint is transferred via the RS485 interface. Control via the
digital I/Os is still active.
3 = USS control word *,
the control signals (enable, rotation direction, etc.) are transferred via the
RS485 interface, the setpoint via the analog input or the fixed frequencies.
4 = USS *
, all control data is transferred via the RS485 interface. The analog and digital inputs have
no function. The setting is required for the external p-box!
5 = CAN setpoint */***
(Option)
6 = CAN control word *
(Option)
7 = CAN *
(Option)
8 = Profibus setpoint */***
(Option)
9 = Profibus control word *
(Option)
10 = Profibus *
(Option)
11 = CAN Broadcast *
(Option)
12 = InterBus setpoint */***
(Option)
13 = InterBus control word *
(Option)
14 =
InterBus * (Option)
15 = CANopen setpoint */***
(Option)
16 = CANopen Control word
* (Option)
17 = CANopen
* (Option)
18 = DeviceNet setpoint */***
(Option)
19 =
DeviceNet Control word * (Option)
20 =
DeviceNet * (Option)
21 =
in preparation
*) Keyboard control (ControlBox, ParameterBox, PotentiometerBox) is blocked, parameterisation is still
possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec), the FI will block
without error message.
***) Permissible settings for using the AS interface.
P510
Interface bus setpoints
always visible
0 ... 8
[ 0 ]
Selection of the interface via which the FI is controlled.
0 = Auto (=P509):
The source of the auxiliary setpoint is
automatically derived from the setting in the parameter
P509 >Interface<
1 = USS
2 = CANbus
3 = Profibus
4 = InterBus
5 = CANopen
6 = DeviceNet
7 =
Reserved
8 = CAN Broadcast
P511
USS baud rate
always visible
0 ... 3
[ 3 ]
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus subscribers must have the
same baud rate setting.
0 =
4800 baud
1 =
9600 baud
2 =
19200 baud
3 =
38400 baud
P512
USS address
always visible
0 ... 30
[ 0 ]
Setting for the inverter address.
Note:
For details about the respective Bus
systems: please refer to the respective
Options descriptions.
BU 0020 = Profibus
BU 0050 = USS
BU 0060 = CAN/CANopen
BU 0070 = InterBus
BU 0080 = DeviceNet
BU 0090 = AS-Interface