2 Assembly and installation
BU 0700 EN
Subject to technical alterations
19
2.10.4 Motor cable (U/V/W/PE)
The motor cable must have a
maximum length of 150m
(Please note also Chapter 8.4 EMC limit value classes). If a shielded
motor cable is used, or the metallic cable duct is well earthed, the
maximum length of 50m
should not be exceeded. For longer
cable lengths , additional output chokes must be used.
For multiple motor use, the total cable length consists of the sum of the individual cable lengths. If the sum of the cable lengths
is too high, one output choke should be used per motor/cable.
Connection terminals cross-section:
SK 700E-151-340-A ... SK 700E-751-340-A
VDE
4mm²
UL/cUL
(AWG
24-10)
SK 700E-112-340-A ... SK 700E-152-340-A
VDE
10mm²
UL/cUL
(AWG
22-8)
SK 700E-182-340-A ... SK 700E-222-340-A
VDE
25mm²
UL/cUL
(AWG
16-4)
SK 700E-302-340-O ... SK 700E-372-340-O
VDE
35mm²
(PE terminals = 16mm
2
) UL/cUL
(AWG
2)
SK 700E-452-340-O ... SK 700E-752-340-O
VDE
25-50mm²
UL/cUL (AWG
4-0)
SK 700E-902-340-O
VDE
95mm²
(no PE terminal)
UL/cUL
(AWG 000)
SK 700E-113-340-O ... SK 700E-163-340-O
VDE
50-150mm²
(PE terminals = 35-95mm
2
) UL/cUL
(AWG
0-300
MCM)
2.10.5 Brake chopper connection up to 22kW (+B/-B)
The connection for the frequency inverter
Æ
brake resistor should be shielded and as short as possible.
Note:
Possible strong heating of the brake resistor should be taken into account.
Connection terminals cross-section:
SK
700E-151-340-A
...
SK 700E-751-340-A
VDE
4mm²
UL/cUL
(AWG
24-10)
SK
700E-112-340-A
...
SK 700E-152-340-A
VDE
10mm²
UL/cUL
(AWG
22-8)
SK
700E-182-340-A
...
SK 700E-222-340-A
VDE
25mm²
UL/cUL
(AWG
16-4)
2.10.6 Brake resistor connection from 30kW (BR+ZW)
The connection for the frequency inverter
Æ
brake resistor should be shielded and as short as possible.
Note:
Possible strong heating of the brake resistor should be taken into account.
Connection terminals cross-section:
SK
700E-302-340-O
...
SK 700E-372-340-O
VDE
16mm²
(add. PE terminals = 16mm
2
) UL/cUL
(AWG
6)
SK
700E-452-340-O
...
SK 700E-752-340-O
VDE
0.75-35mm²
(add. PE terminals = 0.75-35mm
2
) UL/cUL
(AWG
18-2)
SK
700E-902-340-O
VDE
50mm²
(no PE terminals)
UL/cUL
(AWG 4-0)
SK
700E-113-340-O
...
SK 700E-163-340-O
VDE
95mm²
(add. PE terminals = 95mm
2
) UL/cUL
(AWG
000)
Note:
Only one PE terminal is located near the mains connection in the 90kW
device. Further PE connections can be implemented on the device housing.