4.3 Minimum configuration of control connections
... with Basic I/O and ControlBox (Option: SK CU1-BSC + SK TU1-CTR)
If the frequency inverter is to be controlled via the digital and analog inputs, this can be implemented immediately in the delivery
condition. Settings are not necessary for the moment.
A prerequisite is the installation of a customer unit, e.g. the Basic I/O as described here.
Minimum circuitry
Basic parameters
If the current setting of the frequency inverter is not known, loading the factory data is recommended
Æ
P523. The frequency
inverter is parameterised for standard applications in this configuration. If necessary, the following parameters can be modified
(with the Option ControlBox).
P0 - -
Display param eters
_ _ _ _
P1- -
Basic param eters
P2 - -
Motor data
P4 - -
Control terminals
P5 - -
Additional
param eters
P7- -
Inform ation
A
s s
tandar
d
th
e ac
tual
out
put
f
re
q
ue
nc
y
is
d
isp
la
ye
d
P10 2
Acceleration tim e
0 to 99.99 s
Mot
o
r data
S
ee 4.
1 B
as
ic
s
et
tings
P40 0
Funct. analog input
0...10V -frequency-
Operating v alues display
(or operational)
following m ains ON
P10 3
Deceleration tim e
0 to 99.99 s
P10 4
Min. frequency
0Hz to 400Hz
P10 5
Max. frequency
0.1Hz to 400Hz
P4 20
Funct. digital input 1
-ON right-
P523
Load factory data
B
as
ic
- K
undensc
hni
ttst
el
le
X3
.3
X3
.2
X3
.1
01 REL1.1
02 REL1.2
11 VREF 10V
12 AGND /0V
13 AIN1 -
14 AIN1 +
21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
42 VO +15V
Potentiometer, 10kOhm
(Function = P400)
(Range = P104/105)
Switch, ON/OFF
(Function = P420)
Basic customer unit