5.1.5 Control terminals
BU 0700 EN
Subject to technical alterations
85
Parameter
Setting value / Description / Note
Available with option
P435 (P)
Relay 1 scaling
BSC
STD
MLT
BUS
-400 ... 400 %
[ 100 ]
Adjustment of the limit values of the relay functions. For a negative value, the output function will be
output negative.
Current limit = x [%]
⋅
P203 >Motor nominal current<
Torque current limit = x [%]
⋅
P203
⋅
P206 (calculated motor nominal torque)
Frequency limit= x [%]
⋅
P201 >Motor nominal frequency<
Values in the +/-20% range are limited internally to 20%.
P436 (P)
Relay 1 hysteresis
BSC
STD
MLT
BUS
0 ... 100 %
[ 10 ]
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
P441 (P)
Relay 2 function
STD
MLT
0 ... 38
[ 7 ]
This parameter is identical to P434, but refers to P442, P443.
P442 (P)
Relay 2 scaling
STD
MLT
-400 ... 400 %
[ 100 ]
This parameter is identical to P435, but refers to P441, P443.
P443 (P)
Relay 2 hysteresis
STD
MLT
0 ... 100 %
[ 10 ]
This parameter is identical to P436, but refers to P441, P442.
P447 (P)
Offset analog output 2
MLT
-10.0 ... 10.0 V
[ 0.0 ]
This parameter is identical to P417, but refers to P418, P419.
P448 (P)
Function analog output 2
MLT
0 ... 52
[ 0 ]
This parameter is identical to P418, but refers to P417, P419.
P449 (P)
Standardisation analog output 2
MLT
-500 ... 500 %
[ 100 ]
This parameter is identical to P419, but refers to P417, P418.
P458
.. - 01
.. - 02
Analog output mode
MLT
0 ... 1
[ 0 ]
0 =
0...10V / 0...20mA
1 =
2...10V / 4...20mA
This parameter determines the working range of the respective analog
output. Array 01 stands for the 1st analog output, Array 02 for the 2nd.
P460
Watchdog time
always visible
0.0
0.1 ... 250.0 s
[ 10.0 ]
The time interval between the expected watchdog signals (programmable function of digital inputs
P420 ... P425). If this time interval elapses without an impulse being registered, switch off and error
message E012 are actuated.
0.0 (customer error):
Customer error function, as soon as a low-high flank is registered at the input,
the FI switches off with error E012.