CBOX936
INSTALLATION AND PROGRAMMING MANUAL
28
17
INSTALLING THE AUDIO ALARM
1. The alarm has short leads but may be located inside the
box without wiring in additional cable.
2. Locate the alarm output connector per IMAGE 17-1.
3. Ensure red wire is attached to Alarm terminal, and black
wire to GND (ground) terminal.
4. In the event of a hard shutdown, be sure to determine
the problem before resetting the shutdown (pressing the
RESET Button on the control board).
ALARM
OUTPUT
CONN.
IMAGE 17-1:
ALARM OUTPUT
ON CONTROL BOARD
The audio alarm (siren) included in the kit must be connected to the 936 control board to provide an audible
alarm to indicate a hard shutdown of the system, which is triggered by two consecutive entrapment events.
It is a piezoelectric device that can produce a minimum of 100 dB @ 1 foot from enclosure of continuous
sound and is powered by 3-12 VDC. Install as follows:
NOTE:
If using additional cable length for installation of
alarm external to the control box, maximum wire/cable
length is 1000 feet (308.4m).
IMPORTANT!
The installer MUST connect the included audio alarm per these instructions. Installing the audio alarm is
REQUIRED for UL325 compliance.