L1
L2
L3
L4
L5
L6
L7
L8
L1
L2
L3
L4
L5
L6
L7
L8
L1
L2
L3
L4
L5
L6
L7
L8
Input LED
Parameter
LED (level)
value
Description
14
– English
Note: “
” represents the factory setting
All the parameters can be adjusted as required without any contraindication; only the adjustment of the “motor force” could require special care:
• Do not use high force values to compensate for points of abnormal friction on the leaf. Excessive force can compromise the operation of the
safety system or damage the leaf.
• If the “motor force” control is used to assist the impact force reduction system, measure the force again after each adjustment in compliance
with EN standard 12445.
• Wear and weather conditions may affect the movement of the gate, therefore periodic force re-adjustments may be necessary.
7.2.4) Level two programming (adjustable parameters)
The adjustable parameters are factory set as shown in the table 9, with: “
” However, they can be changed at any time as shown in Table 10.
Follow the procedure carefully, as there is a maximum time of 10 seconds between pressing one key and another. If a longer period of time laps-
es, the procedure will finish automatically and memorize the modifications made up to that stage.
1.
Press the key
[Set]
and hold it down (approx. 3 s
3s
2.
Release the
[Set]
key when L1 LED starts flashing
L1
3.
Press key
[
▲
]
or
[
▼
]
to move the flashing LED onto the input LED representing the
parameter which is to be changed
or
4.
Press the key
[Set]
, and hold it down during step 5 and 6
5.
Wait approx. 3 seconds, after which the LED representing the current
level of the parameter which is to be modified will light up.
6.
Press key
[
▲
]
or
[
▼
]
to move the LED representing the parameter value.
or
7.
Release the key
[Set]
8.
Wait 10 seconds before leaving the programme to allow the maximum time to lapse.
10s
Note: Points 3 to 7 can be repeated during the same programming phase in order to set other parameters
Table 10: changing the adjustable parameters
Example
SSS
SSS
SSS
SSS
L6
L7
L8
Open Partially
Maintenance
warning
List of
malfunctions
0,5 m
1 m
1,5 m
2 m
2,5 m
3 m
3,4 m
4 m
Automatic (depending on the severity of the
manoeuvre)
1000
2000
4000
7000
10000
15000
20000
1
a
manoeuvre result
2
a
manoeuvre result
3
a
manoeuvre result
4
a
manoeuvre result
5
a
manoeuvre result
6
a
manoeuvre result
7
a
manoeuvre result
8
a
manoeuvre result
Adjusts the measurement of the partial
opening. Partial opening can be controlled
with the 2nd radio command or with
“CLOSE”, if the “Close” function is present,
this becomes “Open partially”.
Adjusts the number of manoeuvres after
which it signals the maintenance request of
the automation (see paragraph “7.4.3
Maintenance warning”).
The type of defect that has occurred in the
last 8 manoeuvres can be established (see
paragraph “7.6.1 Malfunctions archive”).
Содержание Robus 250
Страница 1: ...NiceHansa Robus Instructions and warnings for installation and use 250 500...
Страница 24: ......
Страница 27: ......