Menu 9.3.3 [S] Cooling system
Select "On" if cooling system is installed (accessory re-
quired).
Setting range: Off, On
Default value: Off
Menu 9.3.4 [S] Heating system 2
Here you select how climate system 2 is installed and if
"Off" is selected in menu 9.3.3 only "Off" or "Heat" can be
selected (accessory required).
Setting range: Off, Heating, H Cooling, Cooling
Default value: Off
Menu 9.3.5 [S] Room unit
Here you select whether the Room unit (RE 10) is to be
activated or not (accessory required).
Setting range: Off, On
Default value: Off
Menu 9.3.6 [S] Room sensor type
Room sensor type is selected here. Menu 6.0 can be ac-
cessed.
Setting range: Off, RG10, RE10
Default value: Off
Menu 9.3.7.0 [S] Forced control
Settings regarding forced control of the relays in the heat
pump are made from the sub-menus in this menu.
Menu 9.3.7.1 [S] Forced control
When ”On” is selected in this menu, the user temporarily
takes control of the relays in the heat pump. The setting
automatically returns to “Off”, 30 minutes after the last
button was pushed or after a restart.
Setting range: Off, On
Default value: Off
Menu 9.3.7.2 – 9.3.7.15 [S] K1 – K14
Here you can select manual control of the relays.
Setting range: Off, On, Auto
Default value: Auto
Menu 9.3.7.16 [S] Alarm 1
Here you can select select manual test of alarm relay 1.
Setting range: Off, On, Auto
Default value: Auto
Menu 9.3.7.17 [S] Alarm 2
Here you can select select manual test of alarm relay 2.
Setting range: Off, On, Auto
Default value: Auto
Menu 9.3.7.18 [S] Return
Return to menu 9.3.7.0.
Menu 9.3.8 [S] Factory setting
Here you can select to restore factory settings in HBS 16.
When returning to the factory settings the language
switches to English.
Setting range: Yes, No
Default value: No
Menu 9.3.9 [S] Operating state
Describes the operating status of HBS 16 and AMS 10.
Shutdown:
Additional heater and heat pump are shutdown
due to an alarm.
Alternating:
The heat pump produces heat and switches,
when necessary, between hot water and climate system.
Combined Mode:
Due to a great heating demand, the
addition is used for hot water and the heat pump produces
heat. The addition assists, when necessary, with heat pro-
duction.
Cooling:
The heat pump produces cooling and switches
between hot water and cooling system, when necessary.
Super cooling:
Only cooling. This is carried out by the heat
pump. Hot water produced by addition.
Hot water:
Only hot water is produced. This is carried out
by the heat pump.
Addition:
The heat pump is off and both hot water and
heat is produced by the addition.
Menu 9.3.10.0 [S] Floor drying setting
Settings for the floor drying program are made in the sub-
menus to this menu.
Menu 9.3.10.1 [S] Floor drying
“On” or “Off” is selected for the floor drying program from
this sub-menu. After time period 1 a switch is made to
time period 2 followed by a return to the normal settings.
Setting range: Off, On
Default value: Off
Menu 9.3.10.2 [S] Period time 1
Selection of the number of days in period 1.
Setting range: 1 – 5 days
Default value: 3 days
Menu 9.3.10.3 [S] Temp. period 1
Selection of the flow temperature in period 1.
Setting range: 15 – 50 °C
Default value: 25 °C
Menu 9.3.10.4 [S] Period time 2
Selection of the number of days in period 2.
Setting range: 1 – 5 days
Default value: 1 days
Menu 9.3.10.5 [S] Temp. period 2
Selection of the flow temperature in period 2.
Setting range: 15 – 50 °C
Default value: 40 °C
Menu 9.3.10.6 [S] Return
Return to menu 9.3.10.0.
Menu 9.3.11 [S] Supply pump exer.
Pump operation can be deactivated here. Pump is in oper-
ation for 2 minutes, 12 hours after last operation.
Setting range: Off, On
Default value: On
59
NIBE™ SPLIT
Miscellaneous
Control
Содержание AMS 10-16
Страница 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Страница 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Страница 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Страница 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Страница 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Страница 86: ...Dimensions Indoor unit HBS 16 600 1040 1140 375 Under Front Right NIBE SPLIT 84 Miscellaneous Dimensions ...
Страница 87: ...Hot water tank HE 30 178 98 418 360 590 5LJKW URQW ERYH 85 NIBE SPLIT Miscellaneous Dimensions ...
Страница 100: ...NIBE SPLIT 98 ...
Страница 101: ...99 NIBE SPLIT ...
Страница 102: ...NIBE SPLIT 100 ...
Страница 103: ......