Menu 8.2.4 [U] Start temp. cooling
The average outdoor air temperature at which the heat
pump (in auto mode) is to start cooling.
When the average outdoor temperature switches over,
Start temp. cooling (menu 8.2.5) cooling starts.
When the average outdoor air temperature falls below
Start temp. cooling – Hysteresis (menu 8.2.5) cooling stops.
Setting range: 10 – 43 °C
Default value: 25 °C
Menu 8.2.5 [U] Hysteresis
See menu 8.2.3 and menu 8.2.4. Also affects control with
room sensor.
Setting range: 1.0 – 10.0
Default value: 1.0
Menu 8.2.6 [N] Return
Return to menu 8.2.0.
Menu 8.3.0 [U] Current limiter
Settings and readings regarding the load monitor are set
in the sub-menus to this menu.
Menu 8.3.1 [U] Fuse size
The setting selected on the EBV card (AA22) knob (R24) is
shown here.
Menu 8.3.2 [U] Max. electric power
The setting selected on the EBV card (AA22) knob (R25) is
shown here.
Menu 8.3.3 [U] Current phase 1
Measured current from phase 1 shown here. If the value
falls below 2.8 A “low” is displayed.
Menu 8.3.4 [U] Current phase 2
Measured current from phase 2 shown here. If the value
falls below 2.8 A “low” is displayed.
Menu 8.3.5 [U] Current phase 3
Measured current from phase 3 shown here. If the value
falls below 2.8 A “low” is displayed.
Menu 8.3.6 [U] Transform. ratio EBV
The transfer value must be defined depending on the
current sensors used for the EBV card.
Setting range: 100 – 1250
Default value: 300
Menu 8.3.7 [U] Return
Return to menu 8.3.0.
Menu 8.5.0 [U] Period settings
Time periods for heating and hot water production are
set in the sub-menus for this menu.
Menu 8.5.1 [U] Period time
The length of time for production of hot water and heating
is set here.
Setting range: 5 – 60 min
Default value: 60 min
Menu 8.5.2 [U] Max time for HW
Here you select how much time of the period time (menu
8.5.1) is to be used to heat the hot water when there is a
need for both heating and hot water.
Setting range: 0 – 60 min
Default value: 40 min
Menu 8.5.3 [U] Return
Return to menu 8.5.0.
Menu 8.6 [N] Return
Return to menu 8.0.
9.0 [S] Service menus
Menu 9.1.0 [S] Heat pump settings
Settings for AMS 10 are made in the sub-menus to this
menu.
Menu 9.1.1 [S] DM start heating
Degree minute setting for start of heat pump, heating.
Setting range: -120 – 0
Default value: -60
Menu 9.1.2 [S] DM start cooling
Degree minute setting for start of heat pump, cooling.
Setting range: 0 – 120
Default value: 60
Menu 9.1.3 [S] Stop temp. heat low
Lower parameter for the heat pump's working range
during heating. It stops below this outdoor air temperat-
ure.
The heat pump is permitted to start again when the out-
door air temperature increases by two degrees over the
set value.
Setting range: -25 – 43 °C
Default value: -25 °C
Menu 9.1.4 [S] Stop temp. heat high
Upper parameter for the heat pump's working range
during heating. It stops above this outdoor air temperat-
ure.
The heat pump is permitted to start again when the out-
door air temperature decreases by two degrees below the
set value.
Setting range: -25 – 43 °C
Default value: 43 °C
Menu 9.1.5 [S] Stop temp. cool low
Lower parameter for the heat pump's working range
during cooling. It stops below this outdoor air temperature.
The heat pump is permitted to start again when the out-
door air temperature increases by two degrees over the
set value.
Setting range: 10 – 43 °C
Default value: 10 °C
57
NIBE™ SPLIT
Miscellaneous
Control
Содержание AMS 10-16
Страница 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Страница 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Страница 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Страница 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Страница 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Страница 86: ...Dimensions Indoor unit HBS 16 600 1040 1140 375 Under Front Right NIBE SPLIT 84 Miscellaneous Dimensions ...
Страница 87: ...Hot water tank HE 30 178 98 418 360 590 5LJKW URQW ERYH 85 NIBE SPLIT Miscellaneous Dimensions ...
Страница 100: ...NIBE SPLIT 98 ...
Страница 101: ...99 NIBE SPLIT ...
Страница 102: ...NIBE SPLIT 100 ...
Страница 103: ......