Menu 9.5.14 [S] Run status
Shows the current operating status of AMS 10
The display can show: Off, Hot water, Heating, Cooling,
Defrost, Oil return or XHW.
Menu 9.5.15 [S] Run status last
Shows the previous operating status for AMS 10
The display can show: Off, Hot water, Heating, Cooling,
Defrost, Oil return or XHW.
Menu 9.5.16 [S] Run status time
The time since the last operating status change.
Menu 9.5.17 [S] Return
Return to menu 9.5.0.
Menu 9.6.0 [S] Heat reg. settings
Settings regarding the heating regulator can be made in
the sub-menus to this menu.
Menu 9.6.1 [S] CompFreq
The current set point value frequency to the compressor
is shown here.
Setting the set point during manual control of the com-
pressor frequency is activated in menu 9.6.2.
AMS 10-16
20 – 85 Hz
Setting range
Menu 9.6.2 [S] Manual CompFreq
Select ”On” to control the compressor frequency manually
in menu 9.6.1.
Setting range: Off, On
Default value: Off
Menu 9.6.3 [S] Max deltaF act/set
The parameter for the heat regulator’s max change of the
set point is selected here.
Setting range: 1 – 10 Hz
Default value: 3 Hz
Menu 9.6.4 [S] CompFreq regP
Select P part for heat regulator.
Setting range: 1 – 60
Default value: 5
Menu 9.6.5 [S] Time min freq start
Select here the time that the compressor is to run at min
speed, after start connecting to the climate system.
Setting range: 10 – 120 min
Default value: 70 min
Menu 9.6.6 [S] Time min freq heat
Select here the time that the compressor is to run at fixed
frequency after shifting to heating. The compressor then
runs at min frequency or at the frequency it had before
hot water charging.
Setting range: 3 – 60 min
Default value: 3 min
Menu 9.6.7 [S] Max diff flow-cFlow
Select here limitation of flow when the degree minute
regulator is way off the set point. Max difference between
flow line front and calculated flow line.
Setting range: 2.0 – 10.0 °C
Default value: 4.0 °C
Menu 9.6.8 [S] CompFreq GMz
Here you select a value for the dynamic in the degree
minute regulator.
Setting range: 95 – 127
Default value: 126
Menu 9.6.9 [S] Return
Return to menu 9.6.0.
Menu 9.7 [S] Reset alarm
Select "Yes" here to reset/acknowledge alarms in HBS 16.
The settings returns to ”No” once the action has been
carried out.
Setting range: Yes, No
Menu 9.8.0 [S] Alarm log
The alarm logs with the last 4 alarms are shown in the sub-
menus of this menu.
Menu 9.8.1.0 – 9.8.4.0 [S] Log 1 – Log 4
The alarm logs are shown in the sub-menus of this menu.
Log 1 is the last alarm, log 2 the next to last, etc.
61
NIBE™ SPLIT
Miscellaneous
Control
Содержание AMS 10-16
Страница 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Страница 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Страница 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Страница 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Страница 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Страница 86: ...Dimensions Indoor unit HBS 16 600 1040 1140 375 Under Front Right NIBE SPLIT 84 Miscellaneous Dimensions ...
Страница 87: ...Hot water tank HE 30 178 98 418 360 590 5LJKW URQW ERYH 85 NIBE SPLIT Miscellaneous Dimensions ...
Страница 100: ...NIBE SPLIT 98 ...
Страница 101: ...99 NIBE SPLIT ...
Страница 102: ...NIBE SPLIT 100 ...
Страница 103: ......