May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Open-circuit or short-circuit on sensor input
Sensor fault, suction gas in AMS 10 (Tho-S).
S. fault Tho-S
E53
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Open-circuit or short-circuit on sensor input
Sensor fault, low pressure transmitter in AMS 10.
S. fault LPT
E54
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Fault in the refrigerant circuit
- Service valve closed
Insufficient refrigerant is detected upon start-up
in cooling mode.
Insufficient refrigerant
E57
- Loose connection sensor (BT15, BT3)
- Defective sensor (BT15, BT3)
- Too little refrigerant
- Defective circuit board for inverter in AMS 10
Failed start for compressor
Inverter error
E59
- Defective control board in AMS 10
- Compressor fault
Hot water alarm
The following alarms block hot water production via AMS 10. The addition is blocked completely.
May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Contactor to internal electricity defective
Too high temperature (>90 °C) on hot water
sensor (BT6).
High HW temp.
8
- Incorrect external addition setting
- Contactor to internal electricity defective
Too high temperature (>90 °C) on immersion
heater sensor (BT19).
High AH temp.
9
- Incorrect external addition setting
- Open-circuit or short-circuit on sensor input
Sensor fault, hot water (BT6).
S. fault HW
34
- Sensor does not work (see "Temperature
sensor" section)
- Open-circuit or short-circuit on sensor input
Sensor fault, immersion heater (BT19).
S. fault AH
35
- Sensor does not work (see "Temperature
sensor" section)
Supply alarm
The following alarms switch off heating/cooling. Only hot water production is permitted.
May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Sensor does not work (see "Temperature
sensor" section)
Too high temperature (>90 °C) on flow line
sensor, system 1 (BT2).
High VBF1
10
- Sensor does not work (see "Temperature
sensor" section)
Too high temperature (>90 °C) on flow line
sensor, system 2.
High VBF2
11
- Open-circuit or short-circuit on sensor input
Sensor fault, supply, system 1 (BT2).
Sensor fault VBF1
36
- Sensor does not work (see "Temperature
sensor" section)
- Open-circuit or short-circuit on sensor input
Sensor fault, supply, system 2.
Sensor fault VBF2
37
- Sensor does not work (see "Temperature
sensor" section)
NIBE™ SPLIT
66
Miscellaneous
Alarm list
Содержание AMS 10-16
Страница 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Страница 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Страница 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Страница 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Страница 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Страница 86: ...Dimensions Indoor unit HBS 16 600 1040 1140 375 Under Front Right NIBE SPLIT 84 Miscellaneous Dimensions ...
Страница 87: ...Hot water tank HE 30 178 98 418 360 590 5LJKW URQW ERYH 85 NIBE SPLIT Miscellaneous Dimensions ...
Страница 100: ...NIBE SPLIT 98 ...
Страница 101: ...99 NIBE SPLIT ...
Страница 102: ...NIBE SPLIT 100 ...
Страница 103: ......