Comfort setting cooling
General
The condition in order for cooling to be activated is that
"On" is selected in menu 9.3.3 Cooling system.
NOTE
The climate system must manage cooling operation.
Settings must be made by the installer when commis-
sioning the system.
If a room sensor is connected, it starts and stops cooling
together with the outdoor temperature. The lowest calcu-
lated supply temperature is set in menu 2.2.4.
Cooling operated from the outdoor sensor in
operating mode AutoK
If the cooling system is set to "On" in menu 9.3.3 and the
outdoor temperature is greater or equivalent to the set
start temperature for cooling in menu 8.2.4, cooling starts.
Cooling stops when the outdoor temperature drops below
the set value minus the set value in menu 8.2.5.
The calculated flow line temperature is determined from
the selected cooling curve in menu 2.2.2 and the offset
for cooling curve, menu 2.2.1. Limitations, which are not
in the diagram, are included in the control system's permit-
ted min temperature.
NOTE
For HBS 10-16 cooling operation is permitted down
to +18°C in the supply temperature to prevent con-
densation in the product.
HBS 11-16 is insulated to prevent condensation for
cooling operation down to +7°C in the supply tem-
perature.
0
0
°C
20
°C
30
5
10
20
framlednings-
temp.
Utetemp
40
15
k=1
k=2
k=3
+ 5
- 5
FÖRSKJUTNING
KYLKURVA (0)
2XWVLGH WHPSHUDWXUH
&DOFXODWHG IORZ
WHPSHUDWXUH
&RROLQJ FXUYH RIIVHW
Controlling cooling mode using the room
sensor
If RG 10 is present, the condition for cooling is that the
room temperature has exceeded the set room temperature
(menu 6.3) by the set value in menu 8.2.5 and that the
outdoor temperature is equivalent to or exceeds the set
outdoor temperature value (menu 8.2.4).
When the room temperature has dropped below the set
room temperature in menu 6.3 by the set value in menu
8.2.5 or the outdoor temperature falls below the set value
in menu 8.2.4 by the set value in menu 8.2.5, cooling
switches off.
NIBE™ SPLIT
10
For Home Owners
Comfort setting cooling
Содержание AMS 10-16
Страница 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Страница 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Страница 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Страница 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Страница 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Страница 86: ...Dimensions Indoor unit HBS 16 600 1040 1140 375 Under Front Right NIBE SPLIT 84 Miscellaneous Dimensions ...
Страница 87: ...Hot water tank HE 30 178 98 418 360 590 5LJKW URQW ERYH 85 NIBE SPLIT Miscellaneous Dimensions ...
Страница 100: ...NIBE SPLIT 98 ...
Страница 101: ...99 NIBE SPLIT ...
Страница 102: ...NIBE SPLIT 100 ...
Страница 103: ......