HEV 300
)'%7
(%
;
;
HEV 500
(%
)'%7
;
;
Explanation
Scale length of
conductor (mm)
Type
Designa-
tion
-
Cable gland
UB1,2,3
18
Terminal block, incoming
mains supply
X1
14
Terminal block, AMS 10-16
X2
12
Terminal block, communica-
tion, AMS 10-16
9
Terminal block, external addi-
tion
X3
12
Terminal block, external immer-
sion heater and temperature
limiter/thermostat emergency
mode FD1-BT30.
X4
12
Terminal block
X100
9
Terminal block
X101
-
Switch
SF1
-
Miniature circuit breaker, con-
trol system
FA1
-
Miniature circuit breaker, out-
door unit
FA2
-
Miniature circuit breaker, ex-
ternal immersion heater
FA3
Connecting the supply
Incoming electricity supply is connected to terminal block
(X1) in HBS 16 via cable gland (UB1). The cable must be
dimensioned according to the applicable norms.
HBS 16 can be connected with either 400 V 3NAC or 230
V 1AC.
400 V 3NAC
: Connect incoming supply according to the
markings on terminal (X1).
NOTE
Depending on the house main fuse and to avoid the
load monitor slowing down the compressor, other
loads in the house should be moved from L3 to L1
and L2.
230 V 1AC
: Install the supplied straps between terminals
L1 and L2 as well as between L2 and L3 on incoming ter-
minal block (X1). Connect incoming supply according to
the terminal markings.
N 0 L L1 L2 L3
PE
L
N
N 0 L L1 L2 L3
PE
L3
L2
L1
N
400 V 3NAC
230 V 1AC
LEK
9 1$&
9 $&
Miniature circuit-breaker
The automatic heating control system, circulation pumps
and their wiring in HBS 16, are internally fuse protected
with a miniature circuit breaker (FA1).
Outdoor module AMS 10-16 and equipment are internally
fuse protected in HBS 16, with a miniature circuit breaker
(FA2).
Temperature limiter
The temperature limiter (FD1) cuts the current supply to
the electrical addition if the temperature rises between
90 and 100°C and can be manually reset.
Resetting
The temperature limiter/emergency mode thermostat
(FD1-BT30) is located in the tanks' electrical connections.
The temperature limiter is reset by firmly pressing in its
button.
NOTE
Reset the temperature limiter, it may have tripped
during transport.
NIBE™ SPLIT
32
For the Installer
Electrical installation
Содержание AMS 10-16
Страница 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Страница 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Страница 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Страница 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Страница 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Страница 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Страница 86: ...Dimensions Indoor unit HBS 16 600 1040 1140 375 Under Front Right NIBE SPLIT 84 Miscellaneous Dimensions ...
Страница 87: ...Hot water tank HE 30 178 98 418 360 590 5LJKW URQW ERYH 85 NIBE SPLIT Miscellaneous Dimensions ...
Страница 100: ...NIBE SPLIT 98 ...
Страница 101: ...99 NIBE SPLIT ...
Страница 102: ...NIBE SPLIT 100 ...
Страница 103: ......