MASTER
TRACE
B.3
Appendix B Display Message
Details - Measured
MESSAGE NO:
M1-12
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 300 V
DISPLAY MODE: All
RESTRICTIONS: Single-pole 1 and 2 point
modules
The displayed value is the measured supply voltage.
MESSAGE NO:
M1-13
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 1000 mA
DISPLAY MODE: All
RESTRICTIONS: None
The displayed value is the ground leakage or ground fault current. If the current
exceeds the value range then “O.L.” is displayed.
Measured Values: Statistics Menu
MESSAGE NO:
M2-01
APPLIES TO:
Interface Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE: Advanced
RESTRICTIONS: None
This message displays the name of the sub-menu when entered.
MESSAGE NO:
M2-02
APPLIES TO:
Interface Module
DEFAULT VALUE:Selected Htr
VALUE RANGE: Set by MODULE RANGE
function
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function selects the heater circuit. Each heater circuit has a unique two-part
Heater Number. The first part is the Module Number and the second part is the
heater circuit within the Control Module. Press [VALUE
ñ
] or [VALUE
ò
] and
then press [STORE] to select a heater circuit. For convenience and to reduce
human error, the Heater Name is also displayed.
MESSAGE NO:
M2-03
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE:
-50 to 500 °C
-58 to 932 °F
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the lowest Heater Control Temperature since the last reset.
If the displayed value is “RTD SHORT”, a value less than the minimum range was
recorded. To reset the displayed value press [RESET]. To reset with all statistics
use RESET STATISTICS function.
MESSAGE NO:
M2-04
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE:
-50 to 500 °C
-58 to 932 °F
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the highest Heater Control Temperature since the last reset.
If the displayed value is “RTD OPEN”, a value greater than the maximum range
was recorded. To reset the displayed value press [RESET]. To reset with all
statistics use RESET STATISTICS function.
HEATER VOLTAGE
120V
&
GROUND FAULT
CURRENT: 5mA
&
MEASURED VALUES:
STATISTICS
&
SELECT HT: 1-1
?
NONAME
&
MIN TEMPERATURE:
3°C
&
MAX TEMPERATURE:
25°C
&
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...