MASTER
TRACE
3.17
Chapter 3 Product Description
3.3.15 ML100 Dedicated Interface Module
Control Power
Power Requirements:
From Control Module ML100 Interface
connector: +5Vdc/0.1A, +8Vdc/0.4A,
-6.5Vdc/1mA
Communications
Port:
1 Dedicated parallel connection
Interconnect:
26-pin IDC ribbon cable
Cable Length:
3 feet maximum
Environment
Approval:
CSA NRTL/C
Class 1, Div.II, Groups A,B,C,D
Class 1, Zone-2, Groups IIC
Operating Range:
-40°C to +60°C
(LCD Display: -20°C to +60°C)
(VFD Display: -40°C to +60°C)
Conformal Coating:
Boards conformal coated for hostile
environments
User Interface
Display:
16-character x 2-line LCD or VFD
Alpha-numeric display
Keypad:
9 tactile keys, polyester faceplate
- Setpoint, measured, status
- Message Up, Message Down
- Value Up, Value Down
- Reset
- Store
Contrast:
Adjustable by potentiometer
Panel Indicators:
Power on
Current heater display on
Serial communication active
System alarm
Process alarm
Bezel
Material:
304 Stainless steel
Mounting:
For mounting on NEMA-12 or NEMA-4
enclosure door. Includes gasketing.
Optional:
304 Stainless steel shroud with plexi-
glass hinged cover to protect keypad
from physical damage.
Specifications subject to change without notice.
3.3.16 MR100 Group Interface Module
Control Power
Power Requirements:
12VA @ 120Vac, 50 or 60Hz
Communications
Ports:
1 Serial network connections
Type:
RS485
Protocol:
Modbus® RTU.
Transmission Rate:
600, 1200, 2400, 4800, 9600 baud.
Interconnect:
2-wire, shielded, twisted pair.
Highway Distance:
4,000 feet without repeater.
Modules per Highway:
(1) MR100 and (30) Control Modules.
Environment
Approval:
CSA NRTL/C
Class1, Div.II, Groups A,B,C,D
Class1 Zone 2, Group IIC
Operating Range:
-40°C to +60°C
(LCD Display: -20°C to +60°C)
(VFD Display: -40°C to +60°C)
Conformal Coating:
Boards conformal coated for hostile
environments
Alarm
Alarm Output:
Programmable for NO or NC contacts
One DC opto-isolated contact
One dry mechanical contact
Alarm Output Rating:
Hazardous Areas:
DC contact: 30Vdc/0.1A, 500mW max
Dry mech contact: 30Vdc/10mA max
250Vac/0.5A max
(not subject to a corrosive environment)
Ordinary Areas:
DC contact: 30Vdc/0.1A, 500mW max
Dry mech contact: 120Vac/1.0A max
30Vdc/0.1A max
Alarm Light Output:
LED Indicator: 12Vdc/30mA
Alarm Messages:
Refer to Control Module Specifications
User Interface
Display:
16-character x 2-line LCD or VFD
Alpha-numeric display
Keypad:
9 tactile keys, polyester faceplate
- Setpoint, measured, status
- Message Up, Message Down
- Value Up, Value Down
- Reset
- Store
Contrast:
Adjustable by potentiometer
Panel Indicators:
Power on
Current heater display on
Serial communication active
System alarm
Process alarm
Bezel
Material:
304 Stainless steel
Mounting:
For mounting on NEMA-4/4X
enclosure door. Includes gasketing.
Optional:
304 Stainless steel shroud with plexi-
glass hinged cover to protect keypad
from physical damage.
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...