MASTERTRACE
Appendix G MR100 for Windows CE
G.5
There is a small Heater Select panel on top of the page. User can select the desired heater via the
module number & heater number drop-down edit boxes in this panel. Once the desired heater is selected,
MR100 will regularly communicate to the selected heater and update all the setpoint edit boxes on the page
with its latest data obtained through communication.
The Setpoint Function Page lists all the necessary setpoint edit boxes and command buttons for
the operation of the selected heater. Some setpoint edit boxes are simply drop-down edit boxes. Some of
them are the combination of edit box and increment/decrement buttons. To change a setpoint using drop-
down edit box or increment/decrement button, it is just a matter of mouse click. To change a setpoint using
edit box, touch the box to enter into the edit field first, and then use keyboard to enter numeric numbers for
setpoint values or texts for heater name.
There is a Copy to other heaters command button in green color on Setpoint Function Page.
User can use this command button to copy all the setpoints of the selected heater to all other heaters in the
communication system. The copied setpoints are: heater enabled, heater setpoint, low & high temperature
alarm, low & high current alarm, high current trip, power limit, ground fault trip, ground fault alarm,
tracecheck cycle time, tracecheck htr on time, heater voltage, heater name, master override, proportional
control, deadband, heater fail-safe state, and manual heater. Since the command could greatly alter the
operation of the entire heat tracing panel, an “Are you sure?” window will pop up to get user’s
confirmation for the execution of this important command.
Baud Rate 1 and Baud Rate 2, located on lower portion of Setpoint Function Page, are 2 drop-
down edit boxes designed to change the selected module’s communication baud rates of serial port 1 and 2,
respectively. User must be very careful about changing control module’s communication baud rate since it
could affect entire MR100 communication system. An “Are you sure?” window will pop up to get user’s
confirmation to change the baud rate.
7. Measurement & Statistics Function Page
Measurement & Statistics Function Page, as shown in Figure G.5, displays all measured values
and statistic data of a selected heater, such as heater current, ground fault current, temperature, maximum
current, minimum temperature, etc. It can be opened via Measurement & Statistics tap.
There is a small Heater Select panel on top of the page. User can use the module number &
heater number drop-down edit boxes in this panel to select the desired heater for monitoring.
All the measured values and statistic data boxes related to the selected heater are displayed on the
page. MR100 will be constantly polling the selected heater to update these boxes with its latest data
obtained through communication. If the communication between MR100 and the selected heater is broken,
all the data boxes would be marked as “N/A”.
Some of the statistic data can be reset individually. To reset a single statistic data, follow these
procedures:
(1) Click on the statistic data box to start the reset action.
(2) Confirm/Cancel the reset action by clicking “Yes/No” box on the confirmation box.
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...