5.14
MASTER
TRACE
Chapter 5 Operation
5.8 Interface Module - MR100 for Windows CE
The MR100 for Windows CE Group Interface Module is
capable of programming and monitoring from one to thirty
Control Modules. It is a “Group” interface because it con-
nects, via a serial cable to several Control Modules. It is
designed to be door-mounted in a NEMA-4/4X enclosure
in an industrial environment. Operator interface is through
the 7” touch screen and the on-screen keyboard. Refer to
Figure 5.12 and Figure 5.13.
5.8.1 Touch Screen and Keyboard:
• D1 Touch Screen: The 7” touch screen is the primary
working area of MR100 for Windows CE. It dislays all
kinds of information which MR100 for WIndows CE gath-
ers from each heat-tracing controller in the network. Re-
fer to Appdendix G - MR100 for Windows CE for the
detailed operation of the touch screen.
• K1 Keyboard: The on-screen keyboard can be activated
or hidden through a simple click on the iCon located atthe
bottom. Quite often in the operation of MR100 for Win-
dows CE, keyboard is needed to input the digital values
for heater setpoints and text characters for heater names.
5.8.2 Terminals & Jumper: Refer to the Typical Wiring
Diagrams for power field connections.
• T1 Alarm Contact (terminals A1 and A2): In hazardous
areas, the dry mechanical output is rated 30Vdc @ 10mA,
250Vac @ 0.25A. In ordinary areas, it is rated 120Vac @
0.5A, 30Vdc @ 0.1A.
• T2 Serial Port (terminals A+ and B-): Standard connec-
tion to an RS-485 data highway via a 2-conductor twisted
pair cable. Maximum cable length with 30 Control Mod-
ules without repeater is 4,000 feet.
• T3 Power Input (te15V and GND): 12Vdc @ 850mA
power input.
• T4 Alarm Light Output (terminals C+ and C-): The output
is rated 12Vdc @ 30mA for an LED type lamp.
• J1Alarm Light LED Selection Jumper: For green LED,
place the jumper cap close to “G” mark. For red LED,
place the jumper cap away from “G” mark.
Figure 5.12 MR100 for Windows CE Group Interface Module, Front View
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...