Chapter 3 Product Description
3.3 Control Module Specifications
3.3.1 MS-1DIN2 Control Module
Temperature Input
Range:
-50°C to +500°C
Accuracy:
±2°C
Repeatability:
±1°C
Sensor:
Two 100 ohm, Platinum, 3-wire RTD
per point
20 ohm maximum lead resistance
Heater Switching
Number of Switches:
One dual pole
Switch Rating:
30A @ 280Vac max
Current Measurement:
0.1 to 30A 3%±0.2A
GF Measurement:
10 to 1000mA 5% ±2mA
Voltage Measurement:
0 to 300Vac 3%±2V
Control Power
Power Requirements:
20VA @ 120Vac, 50 or 60Hz
Communications
Communication Ports:
(1) Parallel Local Interface connection
(2) Serial network connections
Serial Communications
Type:
RS485
Protocol:
Modbus® RTU.
Transmission Rate:
600, 1200, 2400, 4800, 9600 baud.
Interconnect:
2-wire, shielded, twisted pair.
Highway Distance:
4,000 feet without repeater.
Modules per Highway:
(1) Interface and (30) Control Modules.
Measured Values
Temperature:
-50 to 500°C (-58 to 932°F)
Minimum Temperature:
-50 to 500°C (-58 to 932°F)
Maximum Temperature: -50 to 500°C (-58 to 932°F)
Heater Current:
0.1 to 100A
Ground Fault Current:
0.01 to 1.0A
Heater Voltage:
0 to 300Vac
Heater Utilization:
0 to 100%
Power Consumption:
0 to 1,000 MWh
Operating Cost:
0 to $1,000,000.00
Environment
Approval:
CSA NRTL/C for Ordinary areas
Operating Range:
-40°C to +60°C
Conformal Coating:
Boards conformal coated for hostile
environments
Alarm
Alarm Output:
Programmable for NO or NC contacts
One DC opto-isolated contact
One dry mechanical contact
Alarm Output Rating:
DC contact: 30Vdc/0.1A, 500mW max
Dry mech contact: [email protected] max
Alarm Light Output:
LED Indicator: 12Vdc/30mA
Alarm Messages
Temperature:
High Temperature Alarm
Low Temperature Alarm
Current:
Low Current Alarm
High Current Trip
Ground Fault Current:
Ground Fault Current Alarm
Ground Fault Current Trip
Voltage:
Low Voltage Alarm
Hardware:
Self-Check Failure
Switch Shorted
RTD Open
RTD Shorted
User-Settable Options
Heater Status:
Enable or Disable
Heater Name or Tag:
16 Character Alphanumeric
Temperature Units:
°C or °F
Control Strategy:
On or Off
Deadband:
0 to 50C° (0-90F°)
Temperature Setpoint:
0 to 500°C (32 to 932°F)
High Temp Alarm:
0 to 500°C (32 to 932°F)
Low Temp Alarm:
-50 to 500°C (-58 to 932°F)
High Current Alarm:
0.5 to 30A
Low Current Alarm:
0.5 to 30A
High Current Trip:
0.5 to 30A
Ground Fault Alarm:
0.01 to 1.0A
Ground Fault Trip:
0.01 to 1.0A
TraceCheck Interval:
1 to 24 hr.
Low Voltage Alarm:
0 to 300Vac
RTD Control Strategy:
Single, Backup, Highest, Lowest,
Average or High Temperature Cutout
RTD Fail-safe:
Heater On or Heater Off
Master Override Input:
On or Off
Alarm Contacts:
NO or NC for each contact
Alarm Light:
Alarm on, Alarm off, Flash during alarm
then on, Flash during alarm then off
Specifications subject to change without notice.
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...