MASTER
TRACE
A.11
Appendix A Display Message
Details - Setpoints
measurement from the RTD Sampler is transmitted to the control module via either
RS485 cable or RF Modem.
If the option “RTD Transmitter” is selected, the control module uses the temperature
measurement signal transmitted from the RTD Transmitters to control heaters. The
RTD Transmitter is another independent temperature-measurement device. The ac-
tual RTD sensor is to be locally wired to the RTD Transmitter. Since the transmitter
uses just two 18AWG wires to transmit its temperature measurement to the control
module in a form of 4-20mA dc current, it can be located up to 7km away from the
control module. This creates a great deal of flexibility to the RTD wiring process.
Each control point requires a dedicated RTD Transmitter for its temperature meas-
urement. Refer to Appendix F for the operation details of RTD Sampler and RTD
Transmitter.
MESSAGE NO:
S3-15
APPLIES TO:
Interface Module
DEFAULT VALUE: 1200
VALUE RANGE:
600,1200,2400,4800,9600
DISPLAY MODE:
Advanced
RESTRICTIONS: MR100 Interface Module
This function sets the communication baud rate for the MR100 serial port .
MESSAGE NO:
S3-16
APPLIES TO:
Interface Module
DEFAULT VALUE: 1200
VALUE RANGE:
600,1200,2400,4800,9600
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function sets the communication baud rate for serial port #1 of the controller.
If the display interface is an ML100, the baud rate applies to the control module it
is connected to. If the display interface is an MR100, the baud rate applies to
serial port #1 of the module selected.
MESSAGE NO:
S3-17
APPLIES TO:
Interface Module
DEFAULT VALUE: 1200
VALUE RANGE:
600,1200,2400,4800,9600
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function sets the communication baud rate for serial port #2 of the control
module that the ML100 display is connected to. If the display interface is an
MR100, the baud rate applies to serial port #2 of the module selected.
MESSAGE NO:
S3-18
APPLIES TO:
Interface Module
DEFAULT VALUE: alarm:off
VALUE RANGE: alarm:off, alarm:on
flash/on, flash/off
DISPLAY MODE: Advanced
RESTRICTIONS: None
This function determines the response of the alarm light output to an alarm. The
alarm light output is design to drive a 12Vdc LED. If the value is set to “alarm
off”, the alarm light is on in a no alarm condition and turns off when alarms are
present. The “alarm off” setting works best with a green LED for fail-safe mode
where loss of power or a burnt out LED generates an alarm condition. Value
“alarm on”, turns the alarm light off in a no alarm condition and turns on when
alarms are present. Value “alarm flash/on” flashes the alarm light when alarms are
present and turns on the alarm light when there are no alarms. Value “alarm flash/
off” flashes the alarm light when alarms are present and turns off the alarm light
when there are no alarms.
MESSAGE NO:
S3-19
APPLIES TO:
Interface Module
DEFAULT VALUE: MECH:NC
VALUE RANGE: MECH:NO SS:NO
SS:NC
MECH:NO SS:NC
MECH:NC SS:NO
MECH:NC SS:NC
DISPLAY MODE: Advanced
RESTRICTIONS: None
BAUD RATE 2:
1200
?
ALARM LIGHT MODE:
alarm: off
?
ALARM CONTACTS:
MECH:NC
?
SS:NC
?
BAUD RATE 1:
1200
?
BAUD RATE MR100:
1200
?
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...