MASTER
TRACE
B.1
Appendix B Display Message
Details - Measured
MESSAGE NO:
M1-01
APPLIES TO:
Interface Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE: All
RESTRICTIONS: None
This message displays the name of the sub-menu when entered.
MESSAGE NO:
M1-02
APPLIES TO:
Interface Module
DEFAULT VALUE:Selected Htr
VALUE RANGE: Set by MODULE RANGE
function
DISPLAY MODE: All
RESTRICTIONS: None
This function selects the heater circuit. Each heater circuit has a unique two-part
Heater Number. The first part is the Module Number and the second part is the
heater circuit within the Control Module. Press [VALUE
ñ
] or [VALUE
ò
] and
then press [STORE] to select a heater circuit. For convenience and to reduce
human error, the Heater Name is also displayed.
MESSAGE NO:
M1-03
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: on, off, man on,
no: 1 to 9 alarms
DISPLAY MODE: All
RESTRICTIONS: None
The displayed value is the status of the selected heater. It indicates whether the
heater circuit is on or off and the number of alarm messages associated with the
circuit. The heater circuit is in manual override if “man on”is displayed. See
MANUAL HEATER function.
MESSAGE NO:
M1-04
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE:
-50 to 500 °C
-58 to 932 °F
DISPLAY MODE: All
RESTRICTIONS: None
For single-RTD modules, the displayed value is the actual measured temperature
of the RTD sensor for this heater circuit. For dual-RTD modules, the displayed
value is calculated from the actual measured temperatures of both RTD sensors
based on the RTD MODE function. The heater circuit is controlled by comparing
the Heater Control Temperature to the Heater Setpoint. If the temperature is
outside the value range then “RTD OPEN” or “RTD SHORT” is displayed.
MESSAGE NO:
M1-05
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE:
-50 to 500 °C
-58 to 932 °F
DISPLAY MODE: All
RESTRICTIONS: Dual RTD Modules Only
The displayed value is the actual measured temperature of RTD-A sensor for this
heater circuit. It is used to calculate the Heater Control Temperature based on the
RTD MODE function. If the temperature is outside the value range then “RTD
OPEN” or “RTD SHORT” is displayed.
Appendix B Display Message Detail - Measured
Measured Values: Operating Values
MEASURED VALUES:
OPERATING VALUES
SELECT HT: 1-1
?
NONAME
&
HEATER IS on
&
&
no ALARMS
HEATER CONTROL
TEMP: 6°C
&
RTD-A ACTUAL
TEMP: 6°C
&
Содержание MASTERTRACE
Страница 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 51: ...MASTERTRACE 5 15 Chapter 5 Operation Figure 5 13 MR100 for Windows CE Group Interface Module RearView ...
Страница 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Страница 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Страница 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Страница 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Страница 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Страница 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Страница 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...